GE Products BuyLog Smart Catalog
Uninterruptible Power Supplies Energy Connections SG Series 225-300 kVA, Three-Phase with Output Iso Transformer UPS Modules
Section 20
Technical Specifications-UL approved Topology
True on-line, double conversion (VFI) with integral static switch and internal maintenance bypass Advanced IGBT with SVM strategy, microprocessor and DSP controlled at optimal switching frequency True on-line double c onversion, automatic bypass, frequency converter, RPA up to eight units
Technology
Operating Modes
Output Power Rating kVA (at PF=0.6–0.8 lag) 225 300 Output Power Rating (kW) 203 270 Weight w/o Batteries (lbs) 3086 3086
Dimensions WxDxH (inches) 65x32x71 Noise Level dB(A) <67 dB Input Voltage (VAC) 3x480/277 + Neutral ( -20% to +15% without battery discharge)
Input Frequency 60/50 Hz +/-10% Output Voltage (sinusoidal) (VAC) 3x480/277 + Neutral Output Frequency 60/50 Hz +/-0.01%
Output THD at Linear Load <2% Output THD at Non-linear Load <3% Crest Factor 3:1
Overload Capability on Inverter 125% 10 min., 150% 30 seconds Overload Capability on Automatic Bypass 200% 5 min., 110% continuously Output Voltage Regulation Static +/- 1% 0-100% Step Load +/- 3% Overall Efficiency at 100% Load 93% Ambient Operating Temperature 32°-104°F (0°-40°C) Color Black Classifications and Listing UL1778/IP20/NEMA-PE-1/ISO9001
RFI and Surge Protection EN 50091-2 / IEC 62040-2 / IEEE 587 B / FCC Class A compliance 1 Standard Connectivity RS232; programmable alarm contacts; SNMP (optional)
Warranty 12 months 1 FCC compliance feature available as an option. Specifications subject to change without notice.
Notes —UPS Module MUST be fed from 3-ph 4-wire solidly grounded WYE input source. —UPS Module can be configured for 3-wire or 4-wire operation and cabling. See Installation Manual. —UPS Module with EMI Filter meets FCC Class A and IEC 62040-2 Category C2. Std UPS meets IEC 62040-2 Category C3. —TLE & SG UPS Module include one CIC Card. If using both External MBP/MBS Cabinet and Remote Status Panel options, include a 2nd CIC Card in bill of material and pricing. —Paralleled UPS Systems require Module RPA Card Option & RPA Output Board.
SG Series 2 UPS Module, 225kVA/202kW, 480/277V, 60Hz - 0.9 Power Factor
Dimensions W x D x H (in)
Weight (lbs)
Description
Product Number
Single Input Module, 6P Rectifier w/5th THD Filter, IGBT Inverter, Bypass Inductor Single Input Module, 6P Rectifier w/5th THD Filter, IGBT Inverter, Bypass Inductor, Seismic Certified
65 x 32 x 71
3086
UB1022SG444AN54
65 x 32 x 71
3086
UB1022SG444AN54-S
Single Input Module, 6P Rectifier, IGBT Inverter, Bypass Inductor, Broadcast Configuration - No RPA available Single Input Module, 6P Rectifier w/5th THD & EMI Filter, IGBT Inverter, Bypass Inductor
65 x 32 x 71
3086
UB1022SG444AN55
65 x 32 x 71
3211
UB1022SG444AY54
SG Series 2 UPS Module, 300kVA/270kW, 480/277V, 60Hz - 0.9 Power Factor
Dimensions W x D x H (in)
Weight (lbs)
Description
Product Number
Single Input Module, 6P Rectifier w/5th THD Filter, IGBT Inverter, Bypass Inductor Single Input Module, 6P Rectifier w/5th THD Filter, IGBT Inverter, Bypass Inductor, Seismic Certified
65 x 32 x 71
3086
UB1030SG444AN54
65 x 32 x 71
3086
UB1030SG444AN54-S
Single Input Module, 6P Rectifier, IGBT Inverter, Bypass Inductor, Broadcast Configuration - No RPA available Single Input Module, 6P Rectifier w/5th THD & EMI Filter, IGBT Inverter, Bypass Inductor
65 x 32 x 71
3086
UB1030SG444AN55
65 x 32 x 71
3211
UB1030SG444AY54