Standard_Drives_Guide
AF-650 GP General Purpose Drive Standard Specifications
Operation (continued) Output Signals
Keypad Keypad Features
2 - Digital Outputs 24 Vdc (Digital Outputs are used in place of 2 of the Digital Inputs) 2 - Form C Relays rated to 2A at 240 Vac 1 - Analog Output 0/4 to 20mA Relay Output Settings:
LCD Display with 6 Alpha-numeric lines. Multi-Language Support Hot Pluggable, Remote Mount Option, and CopyCat Feature, IP65 rating when remote mounted on enclosure LED's - Green - drive is on, Yellow - indicates a warning, Red - indicates an alarm, Amber - Indicates active Menu keys and H-O-A keys Status - shows status of drive Quick Menu - Enters Quick Start, Parameter Data Check, or Trending Modes Main Menu - Used for programming all drive parameters Alarm Log - Used to display Alarm list Back - Reverts to previous step or layer in parameter structure Cancel - Used to cancel last change or command Info - Displays information about a command, parameter, or function in any display. Hand/Off/Auto - Used to control drive locally or put drive in remote mode Reset - Used to reset Warnings or Alarms Up to 4 Separate complete parameter set-ups are available Trend Speed, Power, Frequency or any value programmed in status display 2 Level Password Protection
No Operation Control Ready Drive Ready Drive Ready in Remote Standby No Drive Warnings Drive Running Drive Running No Drive Warnings Drive Running on Remote Alarm Alarm or Warning At Torque Limit Out of Current Range
Keypad Keys
Below Current Above Current Out of Speed Range Below Speed Above Speed Out of Feedback Range Below Feedback Above Feedback Thermal Overload Warning
Password
Alternate Motor Parameters
AF-650 GP General Purpose Drive
Graphical Trending
Reverse Bus OK Torque Limit and Stopped Brake and no Warning Brake Ready and No Faults Brake Chopper Fault External Interlock Out of External Reference Range
RS485 Modbus RTU Serial Communications Physical Level: EIA/RS485 Transmission Distance: 1640 ft (500m) Node Address: 32 Transmission Speed:
2400, 4800, 9600, 19200, 38400,or 115200 (bits/s)
Transmission Mode: Transmission Protocol
Half Duplex Modbus RTU
Below External Reference Above External Reference Fieldbus Controlling Drive No Alarm Running in Reverse Local Mode Active Remote Mode Active Start Command Active
Character Code: Character Length:
Binary 8 Bits
Error Check:
CRC
Mounting Clearance
All AF-650 GP drives can be mounted Side-by-Side without spacing. For all drives rated 100HP or below allow 3.4 inches (100mm) free space above and below. For all drives rated 125HP and above allow 8.9 inches (225mm) free space above and below.
Hand Mode Active Auto Mode Active
Protective Functions
Line Phase Loss DC Overvoltage DC Undervoltage Drive Overload Motor Overtemperature Motor Thermistor Overtemperature
Torque Limit Overcurrent Ground Fault Short Circuit Control Word Timeout
Brake Resistor Short-Circuited Brake Chopper Short-Circuited Brake Check
DC Link Voltage High DC Link Voltage Low
Internal Fan Fault External Fan Fault Power Board Overtemperature
Missing U Phase Missing V Phase Missing W Phase Internal Fault Control Voltage Fault
Auto Tune Check - Wrong Motor Parameters Auto Tune Low Inom - Motor current is too low Current Limit Mechanical Brake Low Drive Initialized to Default Value Keypad Error No Motor
Soft Charge Fault Auto Tuning Fault Serial Comms Bus Fault Hardware Mismatch Speed Limit
Standard Drives Buyers Guide
www.geindustrial.com
31
Prices and data subject to change without notice