Report No.: AHEE230300050751
Test Details Description – Heating mode Model
AS12FBAHRA(indoor unit) + 1U12MEHFRA(outdoor unit)
Test voltage(V)/ Test frequency(Hz)
230 V, 50 Hz
EN14511-2: 2022/ Table 3: Heating Mode – Standard Rating Conditions Indoor Room Size: 22.34 mm 2 ; Installation Height of Indoor Unit: 2.3 m; Indoor Room Dry Bulb( ℃ )/Wet Bulb( ℃ ) : 20/--; Outdoor Room Dry Bulb( ℃ )/Wet Bulb( ℃ ) : 7/6
Test conditions
Measurement 5 Settings
Air conditioner is set to heating mode, the temperature is set to 20 ℃ , the wind speed is set to max.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 6 Settings
Air conditioner is set to heating mode, the temperature is set to 20 ℃ , the wind speed is set to min.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 7 Settings
Air conditioner is set to heating mode, the temperature is set to 30 ℃ , the wind speed is set to max.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 8 Settings
Air conditioner is set to heating mode, the temperature is set to 30 ℃ , the wind speed is set to min.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Set to ‘ Heating-20 ℃ - max wind speed ’ mode compared to 30 ℃ , can save the energy consumption 1.027 kwh per hour, the ration of fractional energy saving can up to 77%. Set to ‘ Heating-20 ℃ - min wind ’ speed mode compared to 30 ℃ , can save the energy consumption 0.809 kwh per hour, the ration of fractional energy saving can up to 78%.
Comparison of measurement 5&7
Conclusion
Comparison of measurement 6&8