HEATING CABLE
SRM/E Self-Regulating Medium Temperature (cont’d.)
Thermal Output Ratings on Insulated Metal Pipe 1
24
Cable Output vs. Temperature
20
20 W/Ft.
16
15 W/Ft.
12
10 W/Ft.
8
Heat Output (W/Ft.)
8 W/Ft.
5 W/Ft.
4
0
30 50 70 90 110 130 150 170 190 210 230 250
270 290 300
Pipe Temperature (˚F)
Note 1 — Thermal output is determined per IEEE 515-2011 Standard for testing, design installation, and maintenance of electrical resistance heat tracing section 4.1.11 Method C.
Output Wattage at Alternate Voltages (W/Ft.)
% Change In Output
% Change In Output
% Change In Output
Model
208V 3.85
220V 4.25 6.88 8.80 13.50 18.40
277V 6.45 10.24 12.50 18.45 24.40
SRM/E 5 SRM/E 8 SRM/E 10
-23 -20 -17 -15 -12
-15 -14 -12 -10
+23 +22 +20 +19 +19
6.4 8.3
SRM/E 15 12.75 SRM/E 20 17.6
-8
Circuit Breaker Selection (Max. Circuit Lengths in Ft.)
50°F Start-Up (Ft.) -20°F Start-Up (Ft.) 15A 20A 30A 40A 50A 15A 20A 30A 40A 50A 15A 20A 30A 40A 50A 0°F Start-Up (Ft.)
Cable Rating
SRM/E 5-1 SRM/E 5-2 SRM/E 8-1 SRM/E 8-2 SRM/E 10-1 SRM/E 10-2 SRM/E 15-1 SRM/E 15-2 SRM/E 20-1 SRM/E 20-2
180 360 145 285 95 190 70 145 60 115
240 480 190 380 125 255 95 190 75 155
360 720 285 575 190 385 145 290 115 230
375 750 325 650 250 490 190 385 155 305
NR NR NR NR NR NR 210 420 160 350
165 325 135 255 90 165 65 120 50 100
220 430 175 345 110 225 85 175 65 135
330 645 265 520 175 345 125 270 105 200
375 750 325 650 250 490 165 360 140 270
NR NR NR NR NR NR 210 420 160 350
155 310 130 245 85 155 60 115
210 415 165 335 100 215 80 165 65 130
310 620 250 490 170 330 120 260 100 195
375 750 325 650 245 470 150 340 135 255
NR NR NR NR 250 490 210 420 160 335
SELF-REGULATING
45 90
NR = Not Required. Maximum circuit length has been reached in a smaller breaker size. Note — Thermal magnetic circuit breakers are recommended since magnetic circuit breakers could "nuisance trip" at low temperature.
G-17