Chromalox Big Red Book
Heating Cable
2256 HTM 2266 HTM High Temperature Maintenance Self-Regulating Electric Traced Tubing (cont’d.)
Technical Specifications Electrical Specifications Heater Type
Self-Regulating
Heater Insulation Fluoropolymer Max. Continuous Exposure Temp. (Power-On) 250˚F (121˚C) Max. Exposure Temp (Power Off) 366˚F (185˚C) Circuit Length
240 feet @ 120 VAC 480 feet @ 240 VAC
Bus Wire Size (AWG)
16
Power Output
5 watts/foot @ 50˚F 120 VAC or 240 VAC
Alternate Voltage
240 VAC self-regulating heaters may be operated at alternative voltages.
Adjustment Factor
208 VAC 78% 277 VAC 109%
Temperature Rating per N.E.C. 500
T3
2256 Self Regulating Heater - HTM
160
140
1/4” Tube
120
3/8” Tube
100
1/2” Tube
80
Tube Temp (˚F)
3/4” Tube
60
40
-40 -20 0 20 40 60 80
AMBIENT TEMP (˚F)
Product Specifications 2256/2266 HTM/HTM
Tube O.D. 1/4” 3/8” 1/2” 3/4” 1/4” 3/8” 1/2” 1/4” 3/8” 1/2”
Standard Wall Thickness***
Working Pressure @200˚F
Nominal Bundle O.D.
Nom. Wt Lbs/ft.
Max. Bend Radius
Material (1)
ASTM
.030” .032” .035” .049” .035” .035” .035” .040” .062” .062”
#122 DHP Copper #122 DHP Copper #122 DHP Copper #122 DHP Copper
B-68 B-75 B-68 B-75 B-68 B-75 B-68 B-75
1270 psi 880 psi 710 psi 660 psi 4470 psi** 2860 psi** 2100 psi** 75 psi** 50 psi** 75 psi**
1.35” 1.40” 1.50” 1.65” 1.35” 1.40” 1.50” 1.35” 1.40” 1.50”
0.4 0.5 0.6 0.9
8” 9”
10” 12”
316/316L-S/S WLD A-269 316/316L-S/S WLD A-269 316/316L-S/S WLD A-269
0.56 0.60 0.65 0.50 0.53 0.60
8” 9” 8” 9”
10”
PFA PFA PFA
D-6867 D-6867 D-6867
10”
Notes: Minimum recommended installation temperature for PVC -25˚F (-32˚C) ** Values given are for welded, seamless slightly higher
Standard Jacket is Black, 105˚C lead free, LT-FRPVC Alternate Jacket Materials – 125˚C FR-TPE, FRPE, FR-Urethane
***Heavier wall thickness available upon request
LTM Product Rating: 185˚F (85˚C) HTM Product Rating: 250˚F (121˚C)
(1) Other tube materials available
G-108
Made with FlippingBook - Online catalogs