Chromalox Big Red Book
CONTROLS
1040 DINRailMultipleLoopTemperature& ProcessController (cont’d.)
Communication Module
Configuration Port
Chromalox PC configuration protocol for connection to the Chromalox 1040 configuration software.
ModBus Port
Connects to a ModBus RTU fieldbus system. ModBus RTU on a RS485 physical layer.
Protocol
Configuration
Data rate: 4800, 9600, 19200. Parity: none, even or odd. Configured using the Chromalox 1040 con- figuration software.
DeviceNet Port
Connects to a DeviceNet fleldbus ststem.
Protocol
DeviceNet Class 2 slave device.
Configuration
Data Rate 125 kbps, 250 kbps, or 500 kbps. MAC ID 0 to 63 (Defaults 125 kbps, ID 63). Configured using the Chromalox 1040 configuration software, via the configuration port .
PROFIBUS Port
Connects to a PROFIBUS fleldbus system.
Protocol
PROFIBUS DP slave device.
Configuration
Data Rate automatically detected by communication modules from 9.6 kb ps, 19.2 kbps, 45.4 kbps, 93.75 kbps, 1 87.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, and 12 Mbps. 0 -126 (Default = 126). Configured using the Chromalox 1040 configuration software, via the configura- tion port.
Profibus Address
ModBus/TCP Port
Connects to a ModBus/TCP fleldbus system.
Mounting Protocol
DIN rail mounting via supplied interconnect module. Fits DIN standard EN50022, DIN46277-3.
ModBus TCP/IP slave device.
Configuration
10/100 Base T, user-definable IP address. Configured using the Chromalox 1040 configuration software via the configuration port.
Operating Environmental Temperature & RH
32° to 131°F (0° to 55°C), -4° to 176°F (-20° to 80°C) storage, 30% to 90% RH non-condensing.
Power Supply
18 to 30 Vdc (inc ripple). 25 W max.
Protection
lEC IP20. Designed for installation in an enclosure sealed against dust and moisture.
Approvals and Certifications
EMC: Certified to EN61326-1:2006. Safety: Complies with EN61 010-1:2010. UL & cUL. Has received ODVA Declaration of Conformity for DeviceNet.
H-36