Subsystem with Type B Components

Safe failure fraction

Hardware fault tolerance (see note 1)

0

1

2

< 60 %

not allowed

SIL1

SIL2

60 % - < 90 %

SIL1

SIL2

SIL3

90 % - < 99 %

SIL2

SIL3

SIL4

≥ 99 %

SIL3

SIL4

SIL4

Figure 5 – BS EN 61508-2 Table 3

This tables show that SIL 2 with HFT 0 can be claimed for a Type B instrument if it has SFF > 90%. This

is the methodology used by many manufacturers in claims made on their certificates.

Hardware Fault Tolerance Requirements BS EN 61511 Ed 1 – Prior Use

The process sector have been using instrumented system to reduce the risk from potential

hazardous events for many decades and have examples of systems installed before the modern

functional safety standards were published that have a long history of good performance. BS EN

61511 enables the end user to take advantage of this historical performance; this is termed ‘Prior

Use’.

BS EN 61511 Clause 11.4.4 states that the HFT requirements stated in Table 6 may be reduced by 1 if

the hardware is selected on the basis of prior use. This means that a target SIL 2 SIF may use a single

sensor (HFT = 0) if the prior use requirements are met.

The requirements for selection of components based on prior use are detailed in BS EN 61511 Clause

11.5.3, but the main features of this clause include: -

·

Appropriate evidence shall be available that the components are suitable for the safety

instrumented system

·

In the case of field instruments, there may be extensive operating experience

·

Evidence of suitability shall include

o

Demonstration of the performance in similar operating profiles and physical

environments

o

The volume of operating experience

This just acknowledges that different operating and process conditions will affect the instrument

performance; for example a history of good performance on a gas plant does not guarantee the

same level of performance on an oil platform.

Was the inspector correct?

The information provided to the HSE Specialist Inspector contained references to HFT compliance

involving BS EN 61508 and SFF and BS EN 61511 and Prior Use.

The Failure Modes, Effects and Diagnostics Analysis (FMEDA) report provided by the manufacturer

and certification body contained the following table.

λ

SD

λ

SU

λ

DD

λ

DU

SFF

DC

S

DC

D

0 FIT 461 FIT

1129 FIT

358 FIT 81% 0% 75%