Wear Out Phase
• Detection:
– Compare failure numbers with anticipated
numbers on annual basis.
– Inspect sample for signs of degradation
• How to handle:
– Inflate beyond nominal useful life
– Calculate
prevailing
PFD on ongoing basis
– Review SIF where PFD
prevailing
> 2 x PFD
design