What was the problem?
§
Manufacturers certificate and FMEDA report stated that the
device was: -
§
Type B
§
SIL 2 with HFT = 0
§
In the FMEDA report a table of failure rates show
§
SFF = 81%
§
But BS EN 61508 Ed 2 shows that for Type B, SFF>90% is
required for SIL 2, HFT 0
©ABBGroup
October23,2016|Slide23
How can they claim SIL 2 with HFT 0?
§
FMEDA report states
§
Radar Transmitters meet requirements of IEC61511
11.4.4 Prior Use
§
Justified by detailing data from field tracking database
and 100,000,000 hours
§
Report and justification was sent to the HSE Specialist
Inspector for consideration
©ABBGroup
October23,2016|Slide24