Guideline – Automatic Overfill Prevention Systems for Terminal Loading Racks v2 Page 14 of 23

controller, and allowing automatic closure of the automated shutdown valve(s).

Faults detected on the pushbutton, or loss of power should allow unit to fail safe.

8.

Automated shutdown valve(s)

– the automated shutdown valve should

automatically close on detection of fault conditions, either through hard wired

relays or from the loading rack control system. The automated shutdown valve

should ideally be located at ground level on loading bay. There may be one valve

per arm, or one valve per grade depending upon the individual site requirements.

The automated shutdown valve may be either motor, hydraulic or gas operated

and should be fail safe closed under fault/loss of power condition.