Guideline – Automatic Overfill Prevention Systems for Terminal Loading Racks v2 Page 14 of 23
controller, and allowing automatic closure of the automated shutdown valve(s).
Faults detected on the pushbutton, or loss of power should allow unit to fail safe.
8.
Automated shutdown valve(s)
– the automated shutdown valve should
automatically close on detection of fault conditions, either through hard wired
relays or from the loading rack control system. The automated shutdown valve
should ideally be located at ground level on loading bay. There may be one valve
per arm, or one valve per grade depending upon the individual site requirements.
The automated shutdown valve may be either motor, hydraulic or gas operated
and should be fail safe closed under fault/loss of power condition.