Guideline – Automatic Overfill Prevention Systems for Terminal Loading Racks v2 Page 21 of 23
Appendix 1 – Examples of factors that may influence response times
Examples of factors that may influence the times;
A.
•
Where the loss of flow control has been caused by a failure of the flow control
valve and is detected in the preset/batch controller, and this detection feature
has been correctly configured, time A may be short.
•
Where the loss of control is detected by a high level detection in the road
tanker, time A will be longer.
B.
•
The time between the detection of the loss of control of flow and the initiation
of the closure of the automated shutdown valve will normally be short. This
time could be longer or may vary where there is significant electronic
processing prior to the close signal being given, or where the initiation is
delayed by, for example, the dumping of pneumatic pressure.
•
The rate of flow will generally reduce after the pump is stopped. However,
where a centrifugal pump (or other non positive displacement pump) is used,
then any upstream pressure, such as that caused by fluid head in the storage
tank, will continue to drive the gasoline at a constant flow rate. The flow rate
will depend upon the upstream pressure and the diameter and configuration
of pipe work and any orifices.
•
Some preset/batch controller systems are designed to delay the stopping of
the pump until the flow control valve has closed. Depending upon the exact
arrangement, this may delay the stopping of the pump so this occurs later
than shown on the diagram.
C.
•
The speed of closure of the automated shutdown valve will depend upon its
design and configuration. Larger valves generally take longer to close than
smaller valves. Closing a valve too quickly can cause high pressures to be
developed upstream of the valve, with the subsequent risk of damage that
could lead to leakage.
•
The momentum of the gasoline will tend to continue driving the gasoline out
of the pipe work due to the initially high linear speeds of the gasoline at
maximum loading rates.
D.
•
This time between the complete closure of the emergency shutdown valve
and the cessation of all flow will depend on the physical arrangement of the
loading system and the road tanker. For example, fuel may enter the vapour
recovery pipe work from the tanker vapour recovery manifold. A table of
example pipe work capacities for pipe diameters and lengths is given in table
1.
The amount of gasoline stored in pipe work can be estimated using the following
formula:
Volume (litres) = (Pipe diameter (inches) / 2 * 2.54)^2 * 3.14 * pipe length (metres) /10
Example volumes of pipe work are given in table 1