Safety and environmental standards for fuel storage sites

Final report

55

213 The process of risk assessment assesses the level of risk posed by the establishment

as a whole and to inform planning of measures such as tertiary containment and emergency

arrangements. The potential for bund failure from the effects of fire/explosion and failure to retain

liquid due to design and construction aspects needs to be recognised to assess the extent

to which tertiary containment may be required. The greater the deviation from good practice,

the more likely it is bunds will fail and the greater the rate of liquid release from the bund. The

paragraph c arrangement in Table 4 does not require upgrade for fire resistance.

214 Where it is difficult to install product-resistant sealants to ensure a liquid tight seal, for

example due to the condition of the concrete faces of the joint, it may be practicable to create a

new joint with fireproof waterstop on the outside of existing bund wall. This would require two new

concrete pillars joined to the outside of the bund wall either side of the existing bund wall joint.

A fireproof waterstop joint could be installed between the two new pillars which would then form

the new bund wall joint. Care would need to be taken to ensure pillars are supported with suitable

foundations and that any new stresses would not lead to cracking of the existing bund wall.

215 It is recommended that a suitable fire test method be agreed and a test programme of trial

joints be carried out to confirm the observed suitability of these expansion joint arrangements.

216 Figure 11 shows a design for the BSTG wall joint with stainless steel protective plate.

Fire resistant sealant and

flexible backing rod

Stainless steel plate

drilled with oversized

holes for stainless

steel bolts

Fire resistant sealant and

intumescent expansion

joint system and flexible

backing rod

OUTSIDE BUND

INSIDE BUND

Existing bund wall

Figure 11

BSTG wall joint with stainless steel

217 Figure 11 shows a bund wall joint with a stainless steel waterstop.