ame 04-05-15 r001 v1 r11 safety intellipoint_, 7/27/2004

William M. Goble – John C. Grebe

Page 2 of 16

Management summary

This report summarizes the results of the Failure Modes, Effects, and Diagnostic Analysis

(FMEDA) of the Safety IntelliPoint RF™ Series Point Level Switch. A Failure Modes, Effects,

and Diagnostic Analysis is one of the steps to be taken to achieve functional safety certification

per IEC 61508 of a device. From the FMEDA, failure rates and Safe Failure Fraction are

determined. The FMEDA that is described in this report concerns only the hardware of the

Safety IntelliPoint RF™ Series Point Level Switch, electronic and mechanical, including the

probe assembly. For full functional safety certification purposes all requirements of IEC 61508

must be considered.

The Safety IntelliPoint RF™ Series Point Level Switch is a two-wire, 4 – 20 mA smart device

with discrete output levels. It contains self-diagnostics and is programmed to send it’s output a

specified state upon internal detection of a failure. For safety instrumented systems usage it is

assumed that the 4 – 20 mA output is used as the primary safety variable. All other possible

output variants are not covered by this report. The different devices can be equipped with or

without display.

The Safety IntelliPoint RF™ Series Point Level Switch is classified as a Type B

1

device

according to IEC61508, having a hardware fault tolerance of 0. The analysis shows that the

device has a safe failure fraction between 90 and 99% (assuming that the logic solver is

programmed to detect any currents outside the discrete output levels boundaries, see section

4.4) and therefore may be used up to SIL 2 as a single device.

The FMEDA analysis was performed for the High Level Fail Safe setting of the switch (HLFS).

Table 1 lists the failure rates for the Safety IntelliPoint RF™ Series Point Level Switch according

to IEC 61508, assuming that the logic solver is set to detect any currents outside a 1mA range

around the three output levels.

Table 1: Failure rates according to IEC 61508

Safety IntelliPoint RF™ Series

Point Level Switch

sd

su2

dd

du

SFF

High Level Fail Safe application

0 FIT

300 FIT

686 FIT

73 FIT

93.2%

These failure rates are valid for the useful lifetime of the product, see Appendix A.

A user of the Safety IntelliPoint RF™ Series Point Level Switch can utilize these failure rates in

a probabilistic model of a safety instrumented function (SIF) to determine suitability in part for

safety instrumented system (SIS) usage in a particular safety integrity level (SIL). A full set of

failure rates is presented in section 4.5 along with all assumptions.

1

Type B component: “Complex” component (using micro controllers or programmable logic); for details

see 7.4.3.1.3 of IEC 61508-2.

2

It is important to realize that the No Effect failures and Annunciation Undetected failures are included in

the “safe” failure category according to IEC 61508. Note that these failures will not affect system reliability

or safety and should not be included in spurious trip calculations