Standard Drives Buyers Guide

106

Prices and data subject

to change without notice

Capacitors, Arrestors and Harmonic Filters

Line/Load Reactors

Up to 600V

Cabinet

Product Number

GO-52

List Price

W

Wgt

(lbs.)

H D

NEMA 1

Enclosure Style

Type

37GCAB8

$146.00

CAB-8

Wall Mount

8

8 6

7

13.22 13 13.09 31

17 24 18.38 45

17.54 31 20.90 180

37GCAB13V

$240.00

CAB-13V

Floor

37GCAB17V

$650.00

CAB-17V

Floor

37GCAB26C

$1564.00

CAB-26C

Floor

Outline Dimensions

Exact terminal configuration may be different than shown. For exact

terminal configuration contact factory for outline drawing.

Motor Protection

Reactors help to protect motors from the high peak voltages and

fast rise times (dv/dt) which can be experienced in IGBT inverter

applications when the distance between the inverter and motor

is long.

Harmonic Reduction

Because all standard GE Line/Load reactors are compensated for

harmonics (current and frequency), they are extremely effective

at reducing the amount of harmonics which are produced by

a drive/inverter. Use 5% impedance, harmonic compensated

reactors for best reaction of harmonic distortion.

Voltage Spike Protection

A 3% impedance reactor is very effective at protecting against

damage to or nuisance tripping of AC voltage source inverters,

due to voltage spikes.

Voltage spikes on the AC power lines cause elevation of the DC

Bus voltage which may cause the inverter to “trip-off” and indi-

cate an over-voltage protection condition. Use reactors to absorb

these line spikes and offer protection to the rectifiers and DC Bus

capacitors while minimizing nuisance tripping of the inverter.

Typical Harmonic Distortion

of PWM Inverter Without Reactor

With 5% Impedance Reactor

Agency Approvals

—GE line reactors are UL recognized.

—All UL approvals are for USA and Canada.

—UL-506 File #E191687 (1 amp-1200 amps)

—UL-508 File #E191686 (1 amp-1200 amps)

—All higher currents offer UL recognized insulation systems

and construction.

—CE Marked

NEMA 1 Cabinets

All GE Line/Load Reactors are available as either open type or

in a NEMA Type 1 general purpose enclosure. To order a reactor

mounted in a cabinet simply change the second to last digit of

the product number from “0” to “1”. Example 37G 00802 becomes

37G 00812.