Previous Page  39 / 52 Next Page
Information
Show Menu
Previous Page 39 / 52 Next Page
Page Background

DRIVES, MOTORS + SWITCHGEAR

ELECTRICAL PROTECTION + SAF TY

(or derating); Switching functions (switch, switch-disconnector,

Make-first-break-last); Mounting method and special environmental

requirements.

Current rating

For an MCB to be effective it must not trip (must hold) during normal

operation (load dependent) and must trip in time to protect cabling

during abnormal operation (cable dependent). These two conditions

can be expressed as I

n(MCB)

I

n(Load)

and I

(CB Max Trip)

< I

n(Cable)

.

A common misconception is that a 100 A circuit breaker will not

trip at 99,99 A and will trip at 100,01 A. Any over-current device will

have actual trip-points different from its nominal rating. An MCB

certified to SANS-60947 [2] may have a non-tripping current (I

U

) of

105% its rating (I

n

) and a tripping current of 135%.

Start with the load to satisfy I

n(MCB)

I

n(Load)

. If the circuit breaker is

to supply a known singular load, the load’s current rating can be taken

directly. In this case, the circuit breaker could be chosen to provide

protection against overload of the load equipment too.

If the circuit breaker is to supply a combination of loads, the circuit

breaker should be sized to supply the anticipated cumulative load.

This can become complicated for many intermittent loads or unknown

loads e.g. general plug sockets outlets. Sometimes the allowed load

is limited to a reasonable value, simply for economic reasons. In

this case, it is improbable that the circuit breaker will provide effec-

tive protection of the individual loads and therefore each load must

incorporate its own protection.

Also consider inrush effects. Many loads have an increased inrush

current that can last from milliseconds to minutes. A direct-on-line

motor can draw a start-up current of 5 to 10 times its rated current

when first energised. Instead of overrating the circuit breaker (and

subsequently the cable) by the same amount, utilise a circuit breaker

with a time-delay curve that exceeds the inrushmagnitude and period

of the load. This might require selecting a cable with a short time

overload rating in excess of the inrush (e.g. some PVC cables can

temporarily exceed the usual 70°C, up to 90°C or 105°C), otherwise

the useful life of the insulation will be impacted.

With the circuit breaker curve at hand and deratings (if any) ap-

plied, select a cable with appropriate cross sectional area, given the

insulation and installation method, to carry the worst case trip current

and satisfy I

CB Max Trip

< I

nCable

. For building installations, SANS-10142-1

[3] provides guidelines for calculating the conductor capacity. This

includes installation method, ambient temperature, number of cables

in proximity and insulation.

Using a slightly larger cable than neededmakes for a conservative

design. For very long cable runs, it might also be required to increase

the cable size to limit the voltage drop under full load. If the protected

circuit contains branches, each of these cables must individually cor-

relate to the circuit breaker rating, regardless of whether their normal

load will only be a fraction of the total.

Abbreviations/Acronyms

Voltage rating

It goes without saying that the

circuit breaker voltage rating

(U

e

) is determined by the source

voltage. Be sure to select a

breaker to the maximum work-

ing voltage of the system. It is

often overlooked that a lead-

acid battery with nominal 12 V

level can be charged over 14 V,

or that the open-circuit voltage

of PV solar panel array may

be significantly higher than its

nominal usage.

Correctly specify an ac or dc breaker

– these devices are generally not inter-

changeable. With dc the direction of cur-

rent flow is of importance too. Keep in mind

that in battery applications you would need a reverse feedable circuit

breaker, as the battery can both charge and discharge.

The over-voltage category is selected according to the position

in the installation. Surge energy is highest near the service entrance

and will dissipate towards lower levels of distribution. For usual

240 V distribution, preferred withstand voltage (U

IMP

) is 6 kV at the

service entrance, 4 kV in distribution and 2,5 kV at the load, but will

also rely on coordination with suitable Surge Protection Devices

(SPDs) throughout.

Short circuit rating

The source also determines the short-circuit rating (I

CU

and I

CS

) re-

quired, as the prospective short-circuit current depends on the source

voltage and source impedance. In a low voltage mains distribution

board, short-circuit currents of several kiloamperes is possible. Instal-

take note

• A circuit breaker is a critical safety device to protect

people and property where electricity is distributed.

• Its primary function is to protect the distribution system

from reaching damaging temperatures.

• These over-current devices protect us, our homes and

industries.

MCB – Miniature Circuit Breaker

PV

– Photovoltaic

PVC

– Polyvinyl Chloride

SPD

– Surge Protection Device

37

June ‘17

Electricity+Control