Table of Contents Table of Contents
Previous Page  94 / 132 Next Page
Information
Show Menu
Previous Page 94 / 132 Next Page
Page Background

Technical article

March 2017

92

www.read-eurowire.com

As before, the fault can be located with

the well-known propagation velocity: the

result of the calculation is 758m.

DC cable (PE (for DC),

> 100kV)

The test configuration consisted of one

cable on a turntable. The cable was

connected to an adjustable DC source.

The breakdown test was performed

by using a spark gap at the far end of

the cable (

Figure 10

). The voltage was

increased until the spark gap got fired.

The resulting travelling waves were

recorded.

Parameters:

• Cable:

779m

• Capacity:

310nF/km

• Inductivity:

110µH/km

• Voltage:

up to 12 kV, DC, both polarities

• Measurement equipment:

transient recorder for fault location,

broadband divider (resistive-capacitive

attenuator) (

Figure 10

,

Figure 11

)

The same measurements as with the AC

cable were performed.

From

Equation 1

the propagation velocity

v

0

can be calculated as 171.25m/µs. With

that information the cable length

l

1

can

be determined. As a cross check the

propagation velocity

v

0

was calculated

from the measurement with the known

cable length

l

0

.

The maximum deviation from the

reference values is < 0.4 per cent.

Field Tests, Conclusions

The experimental tests have shown

the practical feasibility of the proposed

method for fault location on AC and DC

cables.

They also have shown that damping and

dispersion of the measured signal depend

strongly on the monitored cable.

Nevertheless, the experiments have been

limited to a relatively low voltage and to

a short cable length. There has been no

further knowledge about the behaviour

of cables which are laid in the soil or in the

sea.

It is assumed that the much higher

voltage during test or operation will have

a positive effect on the measured signal. It

is also presumed that the dispersion and

damping on a laid cable is lower than on

the drum or turntable.

Furthermore, the reflection losses as seen

in the measurements should not play a big

role in a real situation.

All of these assumptions are not proven so

far. Therefore, the results of the described

tests can be taken as a first step, which

has to be continued with field tests on laid

cables.

The proposed method might be helpful as

a monitoring tool during commissioning

or routine tests on long cables, but also

as an always-online tool to monitor the a

cable under service conditions.

In case of a fatal breakdown the monitored

signal shall help to find the location of

the fault in a very short time and without

further investigations.

n

References

[1]

CIGRÉ 490. Recommendations for Testing of Long

AC Submarine Cables with Extruded Insulation for

System Voltage above 30 (36) to 500 (550)kV

[2]

CIGRÉ 496. Recommendations for Testing DC

Extruded Cable Systems for Power Transmission at

a Rated Voltage up to 500kV

[3]

IEC 62067. Power cables with extruded insulation

and their accessories for rated voltages above

150kV (Um = 170kV) up to 500kV (Um = 550kV) –

Test methods and requirements

[4]

CIGRÉ 297. Practical aspects of the detection and

location of partial discharges in power cables

[5]

Leißner,

Sebastian,

Untersuchungen

zur

Fehlerortung

an

langen

HVDC-Kabeln,

Diplomarbeit, 2013

[6]

Highvolt data sheet 1.31/4, AC Capacitor, Type WC

Highvolt Prüftechnik Dresden GmbH

Marie-Curie-Straße 10

D-01139 Dresden

Germany

Tel

: +49 351 8425 700

Email

:

sales@highvolt.de

Website

:

www.highvolt.de

Voltage kV

Cable length

l

1

with known

v

0

[m] Velocity

l

1

, with known

l

0

[m/µs]

+ 6.5

778

171.4

- 6.5

776

171.7

+ 11.5

780

170.9

- 11.5

777

171.7

Figure 10

:

DC cable, detail spark gap and

attenuator

Figure 11

:

Measurement equipment

Table 3

:

Calculated cable lengths and propagation velocity

Figure

12

:

Measurement

with

broadband

attenuator and negative DC voltage