P & I Design Ltd.
Instrument Specification
CLIENT:
REV DATE
BY
CHKD
APPD
CLIENT REF.
Simon Storage
A 08.04.14 AMS PJP
PJP
Tank 14 HCL
Seal Sands Terminal
P & I REF.
SI144001_SPC
SHT
1
OF
3
IF NOT SIGNED THIS DOCUMENT IS UNCONTROLLED
ITEM:
Electrical
Component
GENERAL
Tag Number
n/a
Service
See Sheet 2
Area Classification
Zone 1 IIB T4
UNIT
Type
Earth Monitoring System
Functional Safety
SIL 2
Supply
230V ac
Case
Copper free cast alloy
Connections
5 x M20 cable entries
Mounting
Surface
Enclosure Class
IP65
Electrical Classification
ATEX Ex II 2(1) GD EExd [ia] IIC T6
Cerificate Reference
SIRA 09ATEX2047 Issue 2
OUTPUT
Type
I.S. output to earthing clamp
Local Indicators on EExd unit :-
Green = Earth Healthy
Red = Earth Broken
Loop Resistance <10 Ohm.
2 Off 500VA 250V ac 5A max DPST contact for
earth status
OPTIONS
(1)
GRP junction box for clamp complete with stowage
pin. 3 x M20 cable entries
(2)
2 pole stainless steel earthing clamp complete with
10m. spiral wound cable.
Clamp certification Ex 1 GD T6
(3)
Installers Kit – ER2KITA
(4)
Spare Clamp and Cable – IPX90/2B10Q
(5)
Earth-Rite® RTR Tester – ER2/CRT
MANUFACTURERS
Supplier
Newson Gale Ltd
DATA
Model Number
RTRMEA1A3A
DOCUMENTATION
See attached Documentation Specification
REVISION HISTORY
Rev
Description
A
Issued For Procurement (Excludes Options 4 and 5)
ZZ#-ECA2.SPC