4.7

Outcome of Functional Safety Assessments and Outstanding Action status.

See Section 2 for actions from current functional Safety Assessments.

4.8

Review of any management of change or modifications to the systems.

4.8.1 Eastham SIS

The committee discussed the number of modifications required to the SIS at Eastham, often

resulting in one modification impacting on another. It was further established that in order to

complete the Chloroform project a new logic solver would be required, as the existing cannot

handle the analog inputs.

It was agreed to consider a simplification of the SIS, such that any tank IHLA would close

all dockline valves. This should remove a lot of the requirement for modification to the SIS.

ACTION 2016

18: Eastham SIS simplification.