P & I Design Ltd.
Instrument Specification
CLIENT:
REV DATE
BY
CHKD
APPD
CLIENT REF.
Vivergo Fuels Ltd
A 05.09.16 DRP MM
MM
Ethanol Road Loading
B 13.09.16 DRP MM
MM
P & I REF.
VI095009_SPC
SHT
1
OF
3
IF NOT SIGNED THIS DOCUMENT IS UNCONTROLLED
ITEM:
Electrical
Component
GENERAL
Tag Number
See sheet 2
Service
Scully Interface Control Station
Area Classification
Zone 1 IIB T4
UNIT
Type
Cast Enclosure
Supply
110Vac
Case
Aluminium
Connections
1 off gland Area
Mounting
Surface
Enclosure Class
IP66
Electrical Classification
ATEX II 2 G EExd IIB
ADDITIONAL DETAILS
Enclosure to be supplied with:-
12 off SAKR 2.5 terminals.
2 off 2.5 Earth terminals.
1 off Omron relay MKS2PI AC110
1 off Omron relay base PF083A-E
Terminals to be identified with dekafix markers as
per drawing.
Enclosure to be drilled for the following gland
entries.
4 x 20mm (Bottom)
Internal wiring refer to Drawing VI095032_DWG &
B
VI095033_DWG
Labels:
1.
Ident Label will be manufactured from 3 Ply
Traffolyte withTag Number and Service Details
– See Sheet 2.
2.
ATEX Certification Label.
MANUFACTURERS
B
Supplier
JCE
DATA
Model Number
TBA
DOCUMENTATION
See attached Documentation Specification
ZZ#-ECA2.SPC
REVISION HISTORY
Rev
Description
A
Issued for Procurement
B
Internal wiring referencing added