Table of Contents Table of Contents
Previous Page  75 / 242 Next Page
Information
Show Menu
Previous Page 75 / 242 Next Page
Page Background

P & I Design Ltd.

Instrument Specification

CLIENT:

REV DATE

BY

CHKD

APPD

CLIENT REF.

Vivergo Fuels Ltd

A 05.09.16 DRP MM

MM

Ethanol Road Loading

B 13.09.16 DRP MM

MM

P & I REF.

VI095009_SPC

SHT

1

OF

3

IF NOT SIGNED THIS DOCUMENT IS UNCONTROLLED

ITEM:

Electrical

Component

GENERAL

Tag Number

See sheet 2

Service

Scully Interface Control Station

Area Classification

Zone 1 IIB T4

UNIT

Type

Cast Enclosure

Supply

110Vac

Case

Aluminium

Connections

1 off gland Area

Mounting

Surface

Enclosure Class

IP66

Electrical Classification

ATEX II 2 G EExd IIB

ADDITIONAL DETAILS

Enclosure to be supplied with:-

12 off SAKR 2.5 terminals.

2 off 2.5 Earth terminals.

1 off Omron relay MKS2PI AC110

1 off Omron relay base PF083A-E

Terminals to be identified with dekafix markers as

per drawing.

Enclosure to be drilled for the following gland

entries.

4 x 20mm (Bottom)

Internal wiring refer to Drawing VI095032_DWG &

B

VI095033_DWG

Labels:

1.

Ident Label will be manufactured from 3 Ply

Traffolyte withTag Number and Service Details

– See Sheet 2.

2.

ATEX Certification Label.

MANUFACTURERS

B

Supplier

JCE

DATA

Model Number

TBA

DOCUMENTATION

See attached Documentation Specification

ZZ#-ECA2.SPC

REVISION HISTORY

Rev

Description

A

Issued for Procurement

B

Internal wiring referencing added