ConocoPhillips – Bramhall Terminal

Road Loading Safety Instrument System - Functional Safety Assessment

P & I Design Ltd

DOCUMENT NO: SI181001_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: B DATE: 30.03.17

Tel: + 44 (0)1642 617444

PAGE 15 OF 30

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

Alarms in the control room alert the operators that the system has operated. There is a reset

procedure for restarting the SIS. Procedure BRM029.

Document Number 11631/15111-100, Issue 2, dated 20

th

September 2010 details this. This

document is part of the detailed design documentation.

Documented in the Design Basis and in Document Number 11631/15111-100, Issue 2, dated

20

th

September 2010

No user Software is necessary. Not Applicable

There is no override of the sensor or valve as per PSLG recommendations.

Operation of the road loading facility will not be possible in the event of a failure of the SIS

The terminal have considered MTTR. The loss of a single gantry would not bring the terminal

operations to a halt.

The system is designed to fail safe and no dangerous combinations of output states have been

identified.