Hybrid applications of IEC61511 – Laurie Blackmore

Disadvantages include:

§

SIS is

much

bigger than the non-61511 (API) design leading to increased complexity of

operation, maintenance. This increases the risk of systematic faults - the primary

cause of major incidents

§

Testing frequency is still based on API RP14C (3 months transmitters, 1 year SDV‘s)

rather than (longer) IEC61511 intervals. This reduces ability to focus on the high-risk

functions

§

The engineering cost and potential schedule increase associated with IEC61511 is

incurred without the benefit of equipment rationalisation or reduced testing costs.

These increases are considerably less than in the previous case.

Lifecycle/contract issues:

§

Since there is no SIL assessment make sure it is clear in the contract to what functions

these pre-defined SIL‘s apply. What is

Safety

? This can have big impact on

engineering hours and equipment costs.

AVOID THIS DESIGN BASIS WHEREVER POSSIBLE

15

API design but with pre-specified integrity levels for safety functions