Previous Page  37 / 64 Next Page
Information
Show Menu
Previous Page 37 / 64 Next Page
Page Background

Local Fuel – Shoreham Oil Terminal

Gasoline Ship Import – Layers of Protection Analysis

P & I Design Ltd

DOCUMENT NO: LF364002_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: E DATE: 30.07.15

Tel: + 44 (0)1642 617444

PAGE 37 OF 38

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

5.5

ALARP

It is considered that the installation of a SIL2 for overfill is consistent with the intent of the

PSLG Guidelines and that any further risk reduction from further Safety Instrument Systems

would not be required.

5.6

Comparison of LOPA - Local Fuel v VALERO

As part of the sensitivity study the LOPA compared the results and data included in both

LOPA’s.

Description

Local Fuel

Valero

No of Gasoline tanks in scope

2

4

Type of Import conducted

Ship

Ship

Total Number of Imports per year

10

66

Imports conducted out of normal hours

3

Not stated

Average quantity transferred per import

1000m

3

2135m

3

Societal Risk

5.93 x 10

-8

/year

1.23 x 10

-6

/year

Individual Risk

7.8 x 10

-8

/year

7 x 10

-7

/year

Scenario 1

- Overfill of gasoline tank during import from a

ship leading to a potential open vapour cloud explosion

Risk Tolerance Criteria

1.0 x 10

-6

/year

1.0 x 10

-6

/year

Frequency of Mitigated Consequence

5.93 x 10

-8

/year

1.23 x 10

-6

/year

Scenario 2 -

Overfill of gasoline tank during import from a

ship leading to a potential flash fire

Risk Tolerance Criteria

1.0 x 10

-6

/year

1.0 x 10

-5

/year

Frequency of Mitigated Consequence

3.30 x 10

-7

/year

2.06 x 10

-6

/year

Scenario 3

- Overfill of gasoline tank during import from a

ship leading to a potential open vapour cloud explosion, bund

wall damage and a potential MATTE

Risk Tolerance Criteria

1.0 x 10

-6

/year

1.0 x 10

-6

/year

Frequency of Mitigated Consequence

1.58 x 10

-7

/year

9.88 x 10

-7

/year

Valero Scenario 4

- Overfill of gasoline tank during import

from a ship leading to a fire, bund wall damage and a potential

MATTE

Risk Tolerance Criteria

1.0 x 10

-6

/year

Frequency of Mitigated Consequence

4.12 x 10

-7

/year

Valero Scenario 5

,

Local Fuel Scenario 4

- Overfill of

gasoline tank during import from a ship leading to release of

gasoline and a potential MATTE

Risk Tolerance Criteria

1.0 x 10

-6

/year

1.0 x 10

-6

/year

Frequency of Mitigated Consequence

6.59 x 10

-8

/year

4.12 x 10

-7

/year