GE Products BuyLog Smart Catalog

Uninterruptible Power Supplies Energy Connections SG Series 10-150 kVA Three-Phase Battery Cabinets

Section 20

SG UPS Module - 10kVA/8kW (0.80 .pf) - Battery Cabinets (matching)

Qty of Jars Jar Product Number (on 480VDC Bus) 40 / 12HX100FRGN 40 / 12HX150FRGN

Backup Time @ 0.8 .pf

Dimensions W x D x H (in) 27 x 32 x 71 27 x 32 x 71

Weight (lbs)

Product Number

Qty of Cabinets (Strings)

DC CB Size

52 min 60 min

1265 1517

SBA010-1AF-5C-N SBA010-1AF-5E-N

1 1

30A 30A

SG UPS Module - 20kVA/16kW (0.80 .pf) - Battery Cabinets (matching)

Qty of Jars Jar Product Number (on 480VDC Bus) 40 / 12HX100FRGN 40 / 12HX150FRGN 40 / 12HX205-FR 40 / 12HX300-FR

Dimensions W x D x H (in) 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71

Weight (lbs)

Product Number

Qty of Cabinets (Strings)

DC CB Size

Backup Time @ 0.8 .pf

21 min 36 min 53 min 60 min

1265 1517 2025 2761

SBA020-1AF-5C-N SBA020-1AF-5E-N SBA020-1AF-51-N SBA020-1AF-52-N

1 1 1 1

50A 50A 50A 50A

SG UPS Module - 30kVA/24kW (0.80 .pf) - Battery Cabinets (matching)

Qty of Jars Jar Product Number (on 480VDC Bus) 40 / 12HX100FRGN 40 / 12HX150FRGN 40 /12HX205-FR 40 /12HX300-FR 40 / 12HX330-FR

Product Number

Backup Time @ 0.8 .pf

Dimensions W x D x H (in) 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71

Weight (lbs)

Qty of Cabinets (Strings)

DC CB Size

12 min 21 min 33 min 54 min 60 min

1265 1517 2025 3221 4525

SBA030-1AF-5C-N SBA030-1AF-5E-N SBA030-1AF-51-N SBA030-1AF-52-N SBA030-1AF-53-N

1 1 1 1 1

80A 80A 80A 80A 80A

SG UPS Module - 40kVA/32kW (0.80 .pf) - Battery Cabinets (matching)

Qty of Jars Jar Product Number (on 480VDC Bus) 40 / 12HX100FRGN 40 / 12HX150FRGN 40 / 12HX205-FR 40 / 12HX300-FR 40 / 12HX330-FR 40 / 12HX400-FR 40 / 12HX505-FR Qty of Jars Jar Product Number (on 480VDC Bus) 40 / 12HX100FRGN 40 / 12HX150FRGN 40 /12HX205-FR 40 /12HX300-FR 40 /12HX400-FR 40 /12HX540-FR

Product Number

Backup Time @ 0.8 .pf

Dimensions W x D x H (in) 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 44 x 32 x 71 44 x 32 x 71

Weight (lbs)

Qty of Cabinets (Strings)

DC CB Size

1265 1517 2025 2761 3221 3557 4525

SBA040-1AF-5C-N SBA040-1AF-5E-N SBA040-1AF-51-N SBA040-1AF-52-N SBA040-1AF-53-N SBB040-1AF-54-N SBB040-1AF-55-N

1 1 1 1 1 1 1

100A 100A 100A 100A 100A 100A 100A

8 min

15 min 23 min 38 min 45 min 54 min 60 min

SG UPS Module - 50kVA/40kW (0.80 .pf) - Battery Cabinets (matching)

Product Number

Backup Time @ 0.8 .pf

Dimensions W x D x H (in) 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 44 x 32 x 71 44 x 32 x 71

Weight (lbs)

Qty of Cabinets (Strings)

DC CB Size

5 min

1542 2050 2786 3246 3582 4550

SBA050-1AF-5C-N SBA050-1AF-5E-N SBA050-1AF-51-N SBA050-1AF-52-N SBB050-1AF-54-N SBB050-1AF-56-N

1 1 1 1 1 1

125A 125A 125A 125A 125A 125A

10 min 17 min 28 min 41 min 60 min

All run times listed above are based on the manufacturer’s published data, and do not include connector and wiring losses. These run times are approximate and are intended for use as a guide only. Consult factory for guaranteed run times. All cabinets contain Flame Retardant Batteries. 480 Vdc Nominal - 240 cells - 1.67 Final Volts per Cell, except 1.75 Final Volts per Cell over 60 minutes. An external, user supplied junction panel is required when multiple battery systems are to be connected to a single UPS. Each string, in multi-string systems, is individually fused.

Rev. 1/19 Data subject to change without notice

go.abb/industrial

GE Products BuyLog

20-37