GE Products BuyLog Smart Catalog

Uninterruptible Power Supplies Energy Connections SG Series 10-150 kVA Three-Phase Battery Cabinets

Section 20

SG UPS Module - 80kVA/64kW (0.80 .pf)- Battery Cabinets (matching)

Qty of Jars Jar Product Number (on 480VDC Bus)

Product Number

Backup Time @ 0.8 .pf

Dimensions W x D x H (in) 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 44 x 32 x 71 44 x 32 x 71 71 x 32 x 71 88 x 32 x 71

Weight (lbs)

Qty of Cabinets (Strings)

DC CB Size

9 min

1542 2786 3246 4550 4550 7139 7139

SBA080-1AF-51-N SBA080-1AF-52-N SBA080-1AF-53-N SBB080-1AF-54-N SBB080-1AF-55-N SBC080-2AF-53-N SBB080-2AF-55-N

1 1 1 1 1 2 2

40 / 12HX205-FR 40 / 12HX300-FR 40 / 12HX330-FR 40 / 12HX400-FR 40 / 12HX505-FR 80 / 12HX330-FR 80 / 12HX505-FR

200A 200A 200A 200A 200A 200A 200A

14 min 18 min 22 min 31 min 45 min 60 min

SG UPS Module - 100kVA/80kW (0.80 .pf) - Battery Cabinets (matching)

Qty of Jars Jar Product Number (on 480VDC Bus)

Product Number

Backup Time @ 0.8 .pf

Dimensions W x D x H (in) 27 x 32 x 71 27 x 32 x 71 27 x 32 x 71 44 x 32 x 71 44 x 32 x 71 71 x 32 x 71 88 x 32 x 71 88 x 32 x 71

Weight (lbs)

Qty of Cabinets (Strings)

DC CB Size

6 min

2075 2811 2811 3271 4575 7189 9125 9125

SBA100-1AF-51-N SBA100-1AF-52-N SBA100-1AF-53-N SBB100-1AF-54-N SBB100-1AF-56-N SBC100-2AF-53-N SBB100-2AF-54-N SBB100-2AF-56-N

1 1 1 1 1 2 2 2

40 / 12HX205-FR 40 / 12HX300-FR 40 / 12HX330-FR 40 / 12HX400-FR 40 / 12HX540-FR 80 / 12HX330-FR 80 / 12HX400-FR 80 / 12HX540-FR

250A 250A 250A 250A 250A 250A 250A 250A

10 min 13 min 16 min 26 min 35 min 41 min 60 min

SG UPS Module - 120kVA/96kW (0.80 .pf) - Battery Cabinets (matching)

Qty of Jars Jar Part Number (on 480VDC Bus) 40 / 12HX300-FR 40 / 12HX400-FR 40 / 12HX540-FR 80 / 12HX400-FR 80 / 12HX540-FR 120 / 12HX505-FR Qty of Jars Jar Part Number (on 480VDC Bus) 40 / 12HX330-FR 40 / 12HX505-FR 40 / 12HX540-FR 80 / 12HX400-FR 80 / 12HX540-FR 120 / 12HX400-FR 120 / 12HX540-FR

Product Number

Backup Time @ 0.8 .pf

Dimensions W x D x H (in) 27 x 32 x 71 44 x 32 x 71 44 x 32 x 71 88 x 32 x 71 88 x 32 x 71 132 x 32 x 71

Weight (lbs)

Qty of Cabinets (Strings)

DC CB Size

8 min

2811 3271 3607 6542 7214

SBA120-1AF-52-N SBB120-1AF-54-N SBB120-1AF-56-N SBB120-2AF-54-N SBB120-2AF-56-N SBB120-3AF-55-N

1 1 1 2 2 3

300A 300A 300A 300A 300A 300A

12 min 20 min 32 min 49 min 60 min

10821

SG UPS Module - 150kVA/120kW (0.80 .pf) - Battery Cabinets (matching)

Product Number

Backup Time @ 0.8 .pf

Dimensions WxDxH (in) 27 x 32 x 71 44 x 32 x 71 44 x 32 x 71 88 x 32 x 71 88 x 32 x 71 132 x 32 x 71 132 x 32 x 71

Weight (lbs)

Qty of Cabinets (Strings)

DC CB Size

7 min

2811 3607 4575 6542 7214 9813

SBA150-1AF-53-N SBB150-1AF-55-N SBB150-1AF-56-N SBB150-2AF-54-N SBB150-2AF-56-N SBB150-3AF-54-N SBB150-3AF-56-N

1 1 1 2 2 3 3

400A 400A 400A 400A 400A 400A 400A

13 min 14 min 24 min 37 min 41 min 60 min

10821

All run times listed above are based on the manufacturer’s published data, and do not include connector and wiring losses. These run times are approximate and are intended for use as a guide only. Consult factory for guaranteed run times. All cabinets contain Flame Retardant Batteries. 480 Vdc Nominal - 240 cells - 1.67 Final Volts per Cell, except 1.75 Final Volts per Cell over 60 minutes. An external, user supplied junction panel is required when multiple battery systems are to be connected to a single UPS. Each string, in multi-string systems, is individually fused.

Rev. 1/19 Data subject to change without notice

GE Products BuyLog

go.abb/industrial

20-38