SECTION II - GENERAL INFORMATION
2.1 Location Give careful consideration to your Clayton equipment investment and the equipment warranty when selecting an installation location. The equipment should be located within close proximity to neces- sary utilities, such as fuel, water, electricity, and ventilation. General consumption data for each model is provided in Table 1 of Section VI. General equipment layout and dimensions are provided in Table 2 of Section VI. For actual dimensions and consumption information, please refer to the data submitted with each specific order.
NOTE Clayton’s standard equipment is intended for indoor use only. Clayton’s equipment must be protected from weather at all times. The steam generator/fluid heater, and any associated water and chemical treatment equipment must be maintained at a temperature above 45° F (7° C) at all times.
Maintain adequate clearance around your Clayton equipment for servicing needs. Maintain a mini- mum clearance of 60 inches (1.5 m) in front of the equipment, a minimum clearance of 36 inches (1 m) to the left and right sides, and a minimum clearance of 18 inches (0.5 m) to the rear of the equipment. Ample overhead clearance, including clearance for lifting equipment, should be considered in case the coil requires removing. Equipment layout and dimensions are provided in Table 2 of Section VI. Review the Plan Installation drawing supplied with the order for specific dimensions and clearance information.
CAUTION ALL combustible materials must be kept a minimum of 48 inches (1.2 m) from the front and 18 inches (0.5 m) from the top, rear, and sides of the equipment. A mini- mum clearance of 18 inches (0.5 m) must also be maintained around the flue pipe. Flooring shall be non-combustible. This equipment must not be installed in an area susceptible to corrosive or combustible vapors.
2-1
08/11/2016
Sect02_Genrl-xx4_t.fm
Made with FlippingBook - Online catalogs