Chromalox Big Red Book

Packaged Systems

MVSGI High-Capacity SteamGenerator (con'td.)

Options

Deaerator System Feedwater can contain dissolved gases. Dis- solved oxygen and carbon dioxide can be especially corrosive to steam piping, valves, and other parts due to oxide formations and carbonic acid. Deaerators are used to remove such gases and help minimize corrosion throughout the steam network. Each setup is unique so contact Chro- malox to help properly size a system for your application. Generator Feed Unit Larger generator systems require a feed system to provide the proper amount of make-up and return water during various loads, and ensure the the correct liquid level in the generator. A properly designed system is critical to mini- mize factors such as under/overflow, tempera- ture shock, and corrosion, all while maintaining operational flexibility. Each setup is unique so contact Chromalox to help you properly size a system for your ap- plication.

Auto Blowdown System Sediment, minerals, and other contaminates left behind in a generator vessel can reduce operational efficiency and ultimately lead to a shortened operating life. Regularly schedule blowdowns can help elimi- nate such conditions and ensure operational readiness. Refer to the Accessory section for more details Steam Superheater Electric in-line heaters are ideal for increasing steam quality and ensuring 'dry' steam is avail- able for distribution. Proportional power control is used to ensure only the heat needed is provided for the system. Superheaters can be provided pre-mounted or separate for installation at needed locations. Vacuum Breakers Vacuum Breakers are added to prevent the si- phoning of condensate from the system during shutdowns. UL and/or IEC Ratings Available on applicable product designs Higher or Lower Pressure Ratings

Standard Size Specifications Steam Capacity

Heat Rating

Pressure & Temperature Ratings

Part Number

Steam lb/hr Mbh bhp kW Volts

Design Parameters

Max. Operating Conditions

3,466 6,932

3,924 117 1150 7,847 234 2300

022-307547-001 022-307547-002 022-307547-003 022-307547-004 022-307547-101 022-307547-102 022-307547-103 022-307547-104 022-307547-201 022-307547-202 022-307547-203 022-307547-204 022-307547-301 022-307547-302 022-307547-303 022-307547-304

4160

13,864 15,694 468 4600 20,796 23,541 701 6900

250psig@406°F 17.2barg@207°C 235psig@401°F 16.2barg@205°C

5,485

6,209 185 1820

11,001 12,453 371 3650 22,001 24,906 742 7300 33,032 37,393 1,114 10960

6600

3,466 6,932

3,924 117 1150 7,847 234 2300

4160

13,864 15,694 468 4600 20,796 23,541 701 6900

450psig@460°F 31.0barg@237°C 423psig@454°F 29.1barg@234°C

5,485

6,209 185 1820

11,001 12,453 371 3650 22,001 24,906 742 7300 33,032 37,393 1,114 10960

6600

*Generator and Control units can be mounted separately or together based on site location conditions. **Under the U.S. Federal Safe Drinking Water Act, it is unlawful to install or use this product in any service that comes into contact with water for human consumption (including drinking, food, or beverage preparation, hand washing, or teeth brushing). This product is intended exclusively for use in non-potable service.

D-2