Chromalox Big Red Book

CONTROLS

1040 DINRailMultipleLoopTemperature& ProcessController (cont’d.)

Communication Module

Configuration Port

Chromalox PC configuration protocol for connection to the Chromalox 1040 configuration software.

ModBus Port

Connects to a ModBus RTU fieldbus system. ModBus RTU on a RS485 physical layer.

Protocol

Configuration

Data rate: 4800, 9600, 19200. Parity: none, even or odd. Configured using the Chromalox 1040 con- figuration software.

DeviceNet Port

Connects to a DeviceNet fleldbus ststem.

Protocol

DeviceNet Class 2 slave device.

Configuration

Data Rate 125 kbps, 250 kbps, or 500 kbps. MAC ID 0 to 63 (Defaults 125 kbps, ID 63). Configured using the Chromalox 1040 configuration software, via the configuration port .

PROFIBUS Port

Connects to a PROFIBUS fleldbus system.

Protocol

PROFIBUS DP slave device.

Configuration

Data Rate automatically detected by communication modules from 9.6 kb ps, 19.2 kbps, 45.4 kbps, 93.75 kbps, 1 87.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, and 12 Mbps. 0 -126 (Default = 126). Configured using the Chromalox 1040 configuration software, via the configura- tion port.

Profibus Address

ModBus/TCP Port

Connects to a ModBus/TCP fleldbus system.

Mounting Protocol

DIN rail mounting via supplied interconnect module. Fits DIN standard EN50022, DIN46277-3.

ModBus TCP/IP slave device.

Configuration

10/100 Base T, user-definable IP address. Configured using the Chromalox 1040 configuration software via the configuration port.

Operating Environmental Temperature & RH

32° to 131°F (0° to 55°C), -4° to 176°F (-20° to 80°C) storage, 30% to 90% RH non-condensing.

Power Supply

18 to 30 Vdc (inc ripple). 25 W max.

Protection

lEC IP20. Designed for installation in an enclosure sealed against dust and moisture.

Approvals and Certifications

EMC: Certified to EN61326-1:2006. Safety: Complies with EN61 010-1:2010. UL & cUL. Has received ODVA Declaration of Conformity for DeviceNet.

H-36

Made with FlippingBook - Online catalogs