GE Products BuyLog Smart Catalog
Uninterruptible Power Supplies Energy Connections SG Series 225-300 kVA Three-Phase Battery Systems
Section 20
SG 225kVA UPS - 202kW output (0.90 .pf)
Backup Time @ 0.9 .pf
Qty of Cabinets (Strings)
Qty of Jars Jar Part Number 40 / 12HX540 80 / 12HX300 80 / 12HX400 80 / 12HX540 120 / 12HX505 120 / 12HX540 160 / 12HX505 160 / 12HX540 200 / 12HX540
DC CB Size
Dimensions W x D x H (in)
Weight (lbs)
Product Number
5 min 7 min
1 2 2 2 3 3 4 4 5
600A 300A 300A 300A 600A 600A 600A 600A 600A
44.0 x 31.9 x 70.8 54.0 x 31.9 x 70.8 88.0 x 31.9 x 70.8 88.0 x 31.9 x 70.8 132.0 x 31.9 x 70.8 132.0 x 31.9 x 70.8 176.0 x 31.9 x 70.8 176.0 x 31.9 x 70.8 220.0 x 31.9 x 70.8
4885 4600 6567 7239 9850
SBB225-1AF-56-N SBA225-2BR-52-N SBB225-2BR-54-N SBB225-2BR-56-N SBB225-3AF-55-N SBB225-3AF-56-N SBB225-4AF-55-N SBB225-4AF-56-N SBB225-5AF-56-N
12 min 20 min 30 min 33 min 43 min 48 min 62 min
10859 13134 14148 16417
SG 300kVA UPS - 270kW output (0.90 .pf)
Backup Time @ 0.9 .pf
Qty of Cabinets (Strings)
Qty of Jars Jar Part Number 80 / 12HX330 80 / 12HX400 80 / 12HX540 120 / 12HX400 120 / 12HX540 160 / 12HX540 200 / 12HX540 240 / 12HX540 280 / 12HX540
DC CB Size
Dimensions W x D x H (in)
Weight (lbs)
Product Number
5 min 7 min
2 2 2 3 3 4 5 6 7
400A 400A 400A 800A 800A 800A 800A 800A 800A
54 x 31.9 x 7.08 88 x 31.9 x 70.06 88 x 31.9 x 70.06 132 x 31.9 x 70.06 132 x 31.9 x 70.06 194 x 31.9 x 70.06 238 x 31.9 x 70.06 282 x 31.9 x 70.06 326 x 31.9 x 70.06
6000 6617 7289 9925 9925
SBA300-2BR-53-N SBB300-2BR-54-N SBB300-2BR-56-N SBB300-3AF-54-N SBB300-3AF-56-N SBB300-4AF-56-N SBB300-5AF-56-N SBB300-6AF-56-N SBB300-7AF-56-N
12 min 14 min 23 min 33 min 44 min 55 min 67 min
13235 16542 19848 23156
All run times listed above are based on the manufacturer’s published data, and do not include connector and wiring losses. These run times are approximate and are intended for use as a guide only. Consult factory for guaranteed run times. All cabinets contain Flame Retardant Batteries. 480 Vdc Nominal - 240 cells - 1.67 Final Volts per Cell, except 1.75 Final Volts per Cell over 60 minutes. An external, user supplied junction panel is required when multiple battery systems are to be connected to a single UPS. Each string, in multi-string systems, is individually fused.
Rev. 1/19 Data subject to change without notice
go.abb/industrial
GE Products BuyLog
20-45