GE Products BuyLog Smart Catalog
Uninterruptible Power Supplies Energy Connections SG Series 225-300 kVA Three-Phase External Maintenance Bypass Cabinets
Section 20
Series SG UPS - 3 Breaker Matching, Free Standing Maintenance Bypass Cabinet (MBC)
SG UPS kVA 225kVA 225kVA 300kVA 300kVA
UIB CB (Trip Rating)
MIB & MBB CB (Trip Rating)
Height (in)
Weight (lbs)
kAIC Rating @ 480VAC
Width (in)
Depth (in)
Product Number
450AT (80%) 450AT (80%) 600AT (80%) 600AT (80%)
350AT (80%) 350AT (80%) 500AT (80%) 500AT (80%)
35kAIC 65kAIC 35kAIC 65kAIC
30 30 30 30
32.8 32.8 32.8 32.8
71 71 71 71
400 400 400 400
MBC224-354500-L300 MBC224-354500-L600 MBC304-506000-L300 MBC304-506000-L600
Notes on SG Matching MBC: 1. Cabinets are matching height, depth, and black color same as UPS Module 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. Neutral not used in 3w UPS applications. 3. Base MBC includes 3-breaker with mechanical Kirk Key configuration.
For 3-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #15 to "K", example: MBC224-354000-K600 For 2-breaker MBC with mechanical Kirk Key change, the Base MBC, digit #10 & #11 to "00", example: MBC224-350000-L600 For 2-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #10 & #11 to "00" and digit # 15 to "K", example: MBC224-350000-K600
4. Cabinet conduit access via top, bottom, and sides via knockouts. 5. Warranty is 1 year. Leadtime is 4-6 (typical) weeks via sourced supplier.
Series SG UPS - 3 Breaker Non-Matching, Wall Mount Maintenance Bypass Panel (MBP) - Style A
SG UPS kVA 225kVA 225kVA 300kVA 300kVA
UIB CB (Trip Rating)
MIB & MBB CB (Trip Rating)
kAIC Rating @ 480VAC
Width (in)
Depth (in)
Height (in)
Weight (lbs)
Product Number
450AT (80%) 450AT (80%) 600AT (80%) 600AT (80%)
350AT (80%) 350AT (80%) 500AT (80%) 500AT (80%)
35kAIC 35kAIC 35kAIC 35kAIC
40 40 40 40
14 14 14 14
91 91 91 91
557 557 557 557
GS20350-10450-A1S GS20350-10450-A2S GS20500-10600-A1S GS20500-10600-A2S
Notes on SG Non-Matching MBP Wallmount Panelboard: 1. Cabinets are ANSI grey (switchgear) color 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. Neutral not used in 3w UPS applications. 3. Circuit Breaker interlock system is a Kirk Key mechanical, with detailed operational instructions included. Electrick interlock (w/SKRU) is an option. 4. Cabinet conduit access via top and bottom via knockouts. 5. Warranty is 1 year. Leadtime is 4-8 weeks (typical) via GE factory.
Series SG UPS - 3 Breaker, Wall Mounted Maintenance Bypass Panel (MBP) - Style B
SG UPS kVA 225kVA 225kVA 300kVA 300kVA
UIB CB (Trip Rating)
MIB & MBB CB (Trip Rating)
kAIC Rating @ 480VAC
Width (in)
Depth (in)
Height (in)
Weight (lbs)
Product Number
450AT (80%) 450AT (80%) 600AT (80%) 600AT (80%)
350AT (80%) 350AT (80%) 500AT (80%) 500AT (80%)
35kAIC 65kAIC 35kAIC 65kAIC
36 36 36 36
14 14 14 14
48 48 48 48
140 140 140 140
MBP224-354500-L300 MBP224-354500-L600 MBP304-506000-L300 MBP304-506000-L600
Notes on SG Wallmount MBPs: 1. Cabinets are black in color. 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. Neutral not used in 3w UPS applications. 3. Base MBP includes 3-breaker with mechanical Kirk Key configuration.
For 3-breaker MBP with electric interlock (with SKRU) change, the Base MBP, digit #15 to "K", example: MBC224-354000-K600 For 2-breaker MBP with mechanical Kirk Key change, the Base MBP, digit #10 & #11 to "00", example: MBC224-350000-L600 For 2-breaker MBP with electric interlock (with SKRU) change, the Base MBP, digit #10 & #11 to "00" and digit # 15 to "K", example: MBC224-350000-K600 4. Cabinet conduit access top and bottom via knockouts. 5. Warranty is 1 year. Leadtime is 3-5 weeks (typical) via sourced supplier.
Series SG UPS - 4x2 Combo, 3 Breaker Maintenance Bypass Cabinet (MBC) w/Output Isolation Transformer
SG UPS KVA
UIB CB (Trip Rating)
MIB & MBB CB (Trip Rating)
kAIC Rating @ 480VAC
Width (in)
Depth (in)
Height (in)
Weight (lbs)
Product Number
225 225
450AT (80%) 450AT (80%)
350AT (80%) 350AT (80%)
35kAIC 65kAIC
36 36
33 33
71 71
1650 1650
MBC224-354500-L322 MBC224-354500-L622
Notes on SG 4x2 combo MBC: 1. Cabinets are matching depth, height, black color of UPS Module 2. Baseline configuration is 3-Breaker Type, 480/277V 3ph 4w + gnd. K13 DOE2016 Compliant copper transformer, 480V-208/120V 3. Base 4x2 Combo MBC includes 3-breaker with mechanical Kirk Key configuration.
For 4x2 Combo 3-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #15 to "K", example: MBC224-354000-K622 For 4x2 Combo 2-breaker MBC with mechanical Kirk Key change, the Base MBC, digit #10 & #11 to "00", example: MBC224-350000-L622 For 4x2 Combo 2-breaker MBC with electric interlock (with SKRU) change, the Base MBC, digit #10 & #11 to "00" and digit # 15 to "K", example: MBC224-350000-K622 4. Cabinet conduit access top and bottom via knockouts. 5. Warranty is 1 year. Leadtime is 6-8 weeks (typical) via sourced supplier.
Rev. 1/19 Data subject to change without notice
GE Products BuyLog
go.abb/industrial
20-48