August 2017
3-3
City of Morgan Hill
Sewer System Master Plan
assumptions are made for use of St. Venant equations in the modeling software. First, flow is one
dimensional. This means it is only necessary to consider velocities in the downstream direction
and not in the transverse or vertical directions. Second, the flow is gradually varied. This means
the vertical pressure distribution increases linearly with depth within the pipe.
Manning’s Roughness Coefficient (n)
The Manning roughness coefficient ‘n’ is a friction coefficient that is used in the Manning formula
for flow calculation in open channel flow. In sewer systems, the coefficient can vary between
0.009 and 0.017 depending on pipe material, size of pipe, depth of flow, root intrusion,
smoothness of joints, and other factors.
For the purpose of this evaluation, and in accordance with City standards, an “n” value of 0.0
13
was used for both existing and proposed gravity sewer pipes unless directed otherwise by City
staff based on pipe structural condition.
This “n” value is an acceptable practice in
planning
studies.
Partial Flow Criteria (d/D)
Partial flow in gravity sewers is expressed as a depth of flow to pipe diameter ratio (d/D). For
circular gravity conduits, the highest capacity is generally reached at 92 percent of the full height
of the pipe (d/D ratio of 0.92). This is due to the additional wetted perimeter and increased friction
of a gravity pipe.
When designing sewer pipelines, it is common practice to use variable flow depth criteria that
allow higher safety factors in larger sizes. Thus, design d/D ratios may range between 0.5 and
0.92, with the lower values used for smaller pipes. The smaller pipes may experience flow peaks
greater than planned or may experience blockages from debris. The
City’s design standards
pertaining to the d/D criteria are summarized on
Table 3.1
.
During peak dry weather flows (PDWF), the maximum allowable d/D ratio for proposed pipes (all
diameters) is 0.75. The maximum allowable d/D ratio for all existing pipes (all diameters) is 0.90.
The criterion for existing pipes is relaxed in order to maximize the use of the existing pipes before
costly pipes improvements are required.
During peak wet weather flows (PWWF), to avoid premature or unnecessary trunk line
replacements, the capacity analysis allowed the d/D ratio to exceed the dry weather flow criteria
and surcharge. This condition is evaluated using the dynamic hydraulic model and the criteria
listed on
Table 3.1
, which stipulates that the hydraulic grade line (HGL), even during a surcharged
condition, should be at least three feet below the manhole rim elevation.