Handout 11

Restricted© SiemensAG 2013 All rights reserved.

Page 22

InstMC Functional Safety 2016Conference

Systematic Capability and IEC 61511 Ed 2.0

Restricted© SiemensAG 2013 All rights reserved.

Page 23

InstMC Functional Safety 2016Conference

Device Selection for IEC 61511

• IEC 61511 Ed 2.0 :2016 requires us to select devices with sufficient Systematic Safety

Integrity

• Devices assessed against IEC61508:2010 will have a declared Systematic Capability

• Prior use (IEC61511) offers an alternative route.

• SC needs to be considered as part of the overall SIL assessment

11.5.2 General requirements

11.5.2.1 Devices selected for use as part of a SIS with a specified SIL shall be in

accordance with IEC 61508-2:2010 and IEC 61508-3:2010 and/or 11.5.3 through 11.5.6,

as appropriate.

NOTE Devices assessed against IEC 61508-2:2010 and IEC 61508-3:2010 can be applied in accordance with the

requirements for systematic capability in IEC 61508-2:2010.