To avoid duplication of effort, and enable the delivery of the lifecycle information in a format which is

easy for the operation and maintenance teams to follow, we need use systems which simplify the

recording process and can provide the visual formats such as bow-ties. These formats encourage

operator engagement and enables a clearer understanding of the first 2 questions i.e. the different

hazardous events and the barriers which are in place to protect against it.

The following is an example of a typical LOPA assessment:

Target IL Assessment Summary

Safety impact

Scenario

Blockage downstream valve fuel gas scrubber leading 4 times the design

pressure, failure of the vessel and large gas release.

Purpose and Requirement

To prevent overpressure detected by PSHH-001 and close XV-001 in 10 sec.

Risk Type

Safety

Assessment Date

dd-mm-yyyy

Consequence

Fire and or other explosion, potential for single fatality.

Severity

Cd (On-site fatality)

Target Frequency

1.0E-6

LOPA Assessment

Initiating Causes

Ref

Description

Freq(/yr)

Tags

Justification

A

Failure of Control System

0.2

PICA-123 Removed

B

Human Error

0.01

SOP-0001 Removed

C

Spurious Closure of a Downstream Valve

0.1

Removed

D

Blockage of the after filters.

F-111A&B Removed

Independent Protection Layers

Ref

Description

PFDavg

Tags

Justification

1

BPCS Interlock

0.10000

PIC-123

Removed

2

Operator Response BPCS Alarm

0.10000

PAH-321 Removed

3

Pressure Relief

0.01000

PZV-123 Removed

4

Occupancy

0.10000

Removed

5

Probability of Ignition

0.50000

Removed

PFDavg Calculation

Initiating

Cause

Freq

(yrs)

Independent Protection Layers

1

2

3

4

5

6

7

8

I.E.F(/yr)

A

0.2

1.00000 1.00000 0.01000 0.10000 0.50000

1.0E-4

B

0.01

0.10000 1.00000 0.01000 0.10000 0.50000

5.0E-7

C

0.1

0.10000 1.00000 0.01000 0.10000 0.50000

5.0E-6

D

0.10000 1.00000 0.01000 0.10000 0.50000

0.0E+0

Total Event Frequency Fe/yr.

1.1E-4

PFDavg for Safety Instrumented Function, Ft/Fe

9.5E-3

Safety Integrity Level =

SIL 2

To the untrained eye it can be difficult to disseminate the detail contained within this assessment.

However the use of new tools, enable the same information to be automatically represented in a

pictorial view where it becomes clearer of the important of each barrier in protecting against

individual hazardous events and enables operator engagement.