TRANSFORMERS + SUBSTATIONS

For all the efficiency calculations a per-phase load voltage

V

2

of 220<0°

is used. All calculations performed for the per-phase circuit. The load

current

I

2

is given by the following calculation:

I

2

=

rated% ·

θ

(19)

where

θ

is given by the inverse cosines of the power factor, in this

case 30°. The formulas will be shown completely for the 60 % rated

load. The turns ratio

a

for the Y-Y configuration is 220/220 = 1.

At 60 % the per-phase load current in the primary winding is:

I

2

=

rated% ·

θ

(20)

The induced EMF in the secondary winding is:

E

2

=

V

2

+

[

I

2

(

R

]

L

+

jX

L

)

(21)

The induced voltage in the primary winding is given by:

E

1

=

a

E

2

30

(22)

The current in the primary winding of the transformer is given by:

I

p

=

30

(23)

The per-phase source current is thus given by:

I

2

=

I

p

+

E

1

(

+

)

(24)

where

R

c

– is resistance of the core

The per-phase voltage supplied by the source:

V

1

=

E

1

+ [

I

1

(

R

]

H

+

jX

H

)

(25)

The power input is calculated as follows:

P

out

=

R

e

[

V

2

I

2

]

(26)

Lastly, the efficiency calculated by means of equation:

 = 

(27)

The calculated data for the transformer is enclosed in

Table 3

.

Table 3: Transformer parameters.

Parameters

Impedance (

)

R

c

2 450

X

m

j

1707,32

R

H

2,04

R

L

2,04

X

H

j

3,27

X

L

j

3,27

Figure 5: The exact equivalent circuit of the transformer.

The core-loss resistance and the magnetising reactance is much

bigger than the winding resistances and the leakage reactance. The

reactance of the low voltage and high voltage is as expected since the

transformer has a one-to-one ratio and a Y-Y configuration was used.

The practical test was done on a 1 kVA, 380/380 V transformer.

The following measurements were taken down during the laboratory

test (see

Table 4

):

Table 4: The laboratory readings.

Parameters

Open circuit

Short circuit

Voltage (V)

120

20

Current (A)

0,05

1,5

Power 1 (W)

4

12,5

Power 2 (W)

2

15

Total Power (W)

16

27,5

As seen in

Table 4

, the short-circuit test was only done at a rated volt-

age and current and care was taken to not pass the rated current of

the transformer. As expected, there is a great current at a low voltage.

The efficiency of the transformer was calculated at a rated load

of 60 % to 90 % in 5 % increases and can be seen in

Table 5

.

Table 5: Transformer efficiency at different rated loads.

Rated load (%)

Efficiency (%)

60

88,160

65

88,720

70

89,188

75

89,580

80

89,909

85

90,186

90

90.419

s

s

3

3

V

2

V

2

a

R

c

jX

m

I

2

1 1

(

P

out

)

(

P

in

)

• Many plants are served by a supply system that includes

on-site transformers and substations.

• Transformer efficiency is an increasingly important pa-

rameter to understand, and the efficiency improves with

loading (within the specified operating range).

• Open and short circuit tests can be effectively used to

determine the machine parameter, and hence its efficiency.

Electricity+Control

August ‘15