Instrument and Electrical Installation Specification

P & I Design Ltd

DOCUMENT NO: SI003001.INS

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 17/02/09

Tel: 00 44 (0)1642 617444

PAGE 9 OF 14

Fax: 00 44 (0)1642 616447

www.pidesign.co.uk

3.9.2

Installation (Cont.)

Cable joints shall not be used unless specified or on the written authority of the Engineer.

Cores shall be marked to comply with the references given in the cable schedules using

Critchley Z type or equivalent. They shall be identified having black characters reading from

the terminals outwards. Clip-on ferrules will not be accepted.

Insulated cables shall have standard compression type gland of the appropriate size.

Particulaer ATEX certification requirements will be detailed on cable schedules.

Each gland shall be bonded to its cable armouring, where applicable and unless otherwise

specified, and to be complete with earth tag and locknut.

Cables shall be protected against mechanical damage at vulnerable points. This particularly

applies in exposed locations where cables emerge from ground or floor.

3.9.3 Cables in Ground

When excavating trenches for underground cables, due account shall be taken of ground

conditions. Cables in normal ground shall be laid in trenches 500mm deep minimum unless

agreed otherwise. Before any excavation starts, the Contractor shall check if there is any

record of other underground services along the route.

Trench bottoms shall be cleared of irregular and sharp objects before applying bedding.

Cables shall be laid the appropriate distance apart (dictated by rating factors) on a bed of

clean, dry, builders' sand, 75mm deep.

Cables shall be blinded with a similar layer as soon as possible after installation.

The trench shall be backfilled a further 150mm with riddled, excavated spoil.

Interlocking cable tiles or continuous marker tape, giving clear warning or danger, shall be

placed over each cable or closely associated groups of cables.

Backfill to surface shall be allowed to settle before final topping and grading.

Approved route markers shall be installed where cables enter of leave buildings, at changes

of direction and at appropriate intermediate intervals.

Pilot cables shall run continuously with their associated main cable, where the route is

common.