Background Image
Previous Page  33 / 56 Next Page
Information
Show Menu
Previous Page 33 / 56 Next Page
Page Background

EARTHING + LIGHTNING PROTECTION

T

he components used for installing the external lightning protec-

tion system shall meet the mechanical and electrical require-

ments which are specified in the SANS/ IEC 62561 [2] series.

The lightning protection components are categorised according to

their function as follows:

All metallic lightning protection components (clamps, conductors,

air-termination rods, earth electrodes) exposed to weathering must

be subjected to artificial ageing prior to testing. This is to verify the

components` suitability for its intended function.

Lightning protection components are subject to natural weather-

ing and exposure to corrosion; it is therefore necessary to artificially

age the components before conducting other mechanical strength

and electrical property tests.

Testing of Lightning Protection System components

Artificial ageing

Artificial ageing takes place in two steps:

Step one: Salt mist treatment

This test is intended for components or devices which are designed to

withstand exposure to a saline atmosphere. The tests are conducted

in a salt mist chamber where the specimens are tested with a test

level 2 for more than three days. Test level 2 includes three spraying

stages using a 5% sodium chloride (NaCl) solution at a temperature

between 15°C and 35°C followed by a humidity storage at a relative

humidity of 93% and a temperature of 40°C for 20 to 22 hours.

Step 2 : Humid sulphurous atmosphere treatment

This test is used to evaluate the resistance of materials and com-

ponents to condensed humidity containing sulphur dioxide. The

specimens are placed inside a test chamber where they are treated

with a concentration of sulphur dioxide for seven cycles. Each cycle

has a duration of 24 hours consisting of sulphur dioxide treatment

for eight hours followed by a rest period of 16 hours. Thereafter, the

sulphurous atmosphere is replaced. Only components for outdoor

use and components that are buried in the ground are subjected to

ageing or conditioning before testing. Buried components have ad-

ditional requirements and measures that must be considered, e.g.

No aluminium clamps or conductors may be buried in the ground.

Components for indoor use such as equipotential earth bars do not

have to be subjected to ageing or conditioning. The same applies to

components which are embedded in concrete. These components

are often made of non-galvanised steel.

Air termination systems, masts, rods

The size and dimensions of air termination masts and conductors

vary significantly between different structures and different designs,

for example, 2 m or 3 m long masts may be installed on flat roofs

and 25 m telescopic lightning protection masts may be installed in

explosive areas. SANS / IEC 62561-2 [2] specifies the minimum cross

sections and allowable materials with the corresponding electrical

and mechanical features for each type of air termination mast. For

longer air termination masts, the bending resistance of the air ter-

mination mast and of the stability of the complete air termination

system has to be provided for by means of a static calculation. The

required cross sections and materials must be selected based upon

these stress calculations. Wind speeds and wind loads also have to

be taken into account.

Connection components

The connection components are simply called ‘clamps’ and the

clamps are used to connect various parts of the lightning protection

system together (down conductor to air termination system etc).

There are therefore many different clamp combinations that are

possible. In the case of lightning current loading, clamps are subject

to electrodynamic and thermal testing, which highly depend on the

type of conductor and the clamping connection. The clamps also

allow for the connection of different types of conductors, these dif-

ferent materials all have differing mechanical strengths and thermal

properties. This is particularly evident for stainless steel connection

components, where due to the low conductivity, high temperatures

Test combinations

for MV clamps.

27

October ‘15

Electricity+Control