Switchgear

2

Aftermarket Catalog

2-3

www.geelectrical.com

Prices and data subject

to change without notice

Low Voltage Power and DC Circuit Breakers

Gerapid High Speed DC Circuit Breakers

Technical Data for Rectifier Circuit Breaker Models 8007R and 10007R

Breaker type

Gerapid 8007R

Gerapid 1007R

Arc chute type

1x2

1x3

1x2

1x3

Rated current

In/A

6,000

6,000

8,000

8,000

Rated operating voltage

Ue/V

800

1,200

800

1,200

Rated insulation voltage

Ui/V

2,000

2,000

2,000

2,000

120 min./A

7,200

7,200

9,600

9,600

Short time current

2 min./A

8,000

8,000

16,000

16,000

20 sec./A

12,000

12,000

24,000

24,000

Mechanical endurance

ops.

10,000

1

10,000

1

10,000

1

10,000

1

Total weight approx.

kg

220

220

220

220

1

With regular maintenance 100,000 ops.

Figure 3. Gerapid 8007R and 10007R Rectifier CB, 1X2 Arc Chute, 800VDC

(Dimensions in mm)