Rolling sphere method

In accordance with a lightning protection level 1 system a sphere with

a radius of 20 m was used to determine the height and positioning

of the air terminals.

There are two applicable distances between the air terminals; namely

12 m apart and 16 m apart. The sag of the sphere (20 m radius - LPL1)

is calculated using the following formula:

P = r - [r² - (d/2)²]

Where:

P

= Penetration depth (sag)

r

= Radius of sphere (20 m)

d

= Distance between air terminals

The calculated sag between the air terminals is therefore:

- 12 m distance = 0,92 m

- 16 m distance = 1,67 m

The area between the air terminals is therefore covered via the rolling

sphere method of protection.

Isolated air termination system

Air termination masts and brackets

In order to comply with the design requirements, i.e. two 3 m masts

to be installed to the top of the steel LED frames, specialised mast

brackets had to be designed and manufactured to house the 3 m

long HVI power masts.

Down conductor system

Each mast location is equipped with two HVI power down conductors

that run from the mast connection point to the zero potential con-

nection point (concrete steel reinforcing). The HVI down conductors

are fixed to the structural steelwork (I-Beams) by means of stainless

steel clamps and brackets.

Installation of HVI Down conductors.

Earthing and equipotential bonding

The correct earthing and equipotential bonding of the Lumen light-

ning protection system is imperative for the effective protection of

the LED screens. To this end the following measures were employed:

• The HVI conductors were positively bonded to the concrete steel

reinforcing of the structure at a level below the LED frames

• The concrete steel reinforcing was tested in numerous positions

and found to be electrically continuous with various parallel paths

to earth

• The use of the concrete steel reinforcing vastly increases the cur-

rent division capabilities of the entire lightning protection system

Earthing of HVI power conductors.

Equipotential bonding

The semi-conductive sheath of the HVI power conductors were equi-

potentially bonded to the electrical earthing system at a level below

the LED frames. In turn the electrical earthing system was bonded to

the concrete steel reinforcing at ground floor level. The LED screens

and frames are equipotentially bonded to the electrical earthing

system via the electrical reticulation.

In order for the HVI system to work properly it is imperative that

this equipotential bonding be performed.

3m Air

Terminal

Top of Steelwork

S= 1,67m

HVI Power

Conductor

PVC Insulated

Copper Conductor

Mini Earth Bar

Concrete Steel

Reinforcing

Clamped

Connection To

Reinforcing

r = 20m

16m

Electricity+Control

April ‘15