CDOIF

Chemical and Downstream Oil

Industries Forum

CDOIF is a collaborative venture formed to agree strategic areas for

joint industry / trade union / regulator action aimed at delivering

health, safety and environmental improvements with cross-sector

benefits.

Guideline – Demonstrating Prior Use v4

Page 4 of 30

1.

EXECUTIVE SUMMARY

The final report of the Process Safety Leadership Groups (PSLG) safety and

environmental standards for fuel storage sites was published in December 2009.

Appendix 4 of that report provides guidance on the architecture and design of automatic

overfill protection systems for bulk gasoline storage tanks, one of the systems (or layers

of protection) necessary to achieve the target Safety Integrity Level (SIL) level identified

through the risk assessment.

The PSLG report provides supplementary guidance to the British Standard on the

design, operation and maintenance of safety instrumented systems (for example an

automatic overfill protection system) BS EN 61511, Functional safety – Safety

instrumented systems for the process industry sector.

For a safety instrumented function designed to achieve a specific safety integrity level,

BS EN 61511 has architectural requirements for the subsystems that comprise that

safety instrumented function (sensors, logic solver and final elements). These

architectural requirements are in addition to the failure measure requirements for the

intended safety integrity level - BS EN 61511 Clause 11.4. The architectural

requirements are expressed in terms of hardware fault tolerance (the number of

dangerous failures that a subsystem can tolerate and still perform its function as

intended).

If the end user wishes to reduce the hardware fault tolerance requirements for a specific

safety instrumented function, the end user can gather evidence to meet the "Prior Use"

requirements described in BS EN 61511 Clause 11.5.3. This allows the end user to

reduce the hardware fault tolerance requirements by 1 - see BS EN 61511 Clause

11.4.4. The demonstration of "Prior Use" in BS EN 61511 is solely related to allowing a

modification of the hardware fault tolerance needed for a specific safety integrity level.

A working group was commissioned under CDOIF to develop this guideline to assist

users in preparing a case for demonstration of prior use. This is not intended to be

prescriptive in defining the mechanism by which prior use should be demonstrated, but

aims to highlight key factors that should be considered.