CDOIF

Chemical and Downstream Oil

Industries Forum

CDOIF is a collaborative venture formed to agree strategic areas for

joint industry / trade union / regulator action aimed at delivering

health, safety and environmental improvements with cross-sector

benefits.

Guideline – Demonstrating Prior Use v4

Page 20 of 30

ID

Component

Description

Function

Failure Mode Sub-system Effects

Detection Method

Detected

Failure

Rate

FTD/FTS

Mitigation

1 Interface relay

Provides shutdown

function to MCC

Fail to respond

(Coil open

Circuit)

Open circuit is the

shutdown condition for

the MCC

Hardwired logic circuit

Immediate

0.0002

FTS

All connected devices will be

driven to safe state. Proof Test

shall also identify failed relay.

2 Interface relay

Provides shutdown

function to MCC

Fail to respond

(Coil Short

Circuit)

Coil Short Circuit will

de-energise the

contacts, which is the

shutdown state for the

MCC

Hardwired logic circuit

Immediate

0.0002

FTS

All connected devices will be

driven to safe state. Proof Test

shall also identify failed relay

.

3 Interface relay

Provides shutdown

function to MCC

Contacts failed

open circuit

Open circuit is the

shutdown condition for

the MCC

Hardwired logic circuit

Immediate

0.00003

FTS

All connected devices will be

driven to safe state. Proof Test

shall also identify failed relay.

4 Interface relay

Provides shutdown

function to MCC

Contacts failed

short circuit

None

None

Latent

0.00001

FTD

Proof Test is required to identify

failed relay

.

Table 2 – Example Failure Modes Analysis