Table of Contents Table of Contents
Previous Page  45 / 648 Next Page
Information
Show Menu
Previous Page 45 / 648 Next Page
Page Background

Safety and environmental standards for fuel storage sites

Final report

44

Option

Advantages

Disadvantages

Fire resistance Cost**

Fibreglass

Easy application

––

Suited to small areas

––

Hydrocarbon resistance

––

Inflexibility needs to be

––

catered for in design

to allow for thermal

movements and

avoid overstress and

de-bonding

Low

––

May require

––

additional fire

protection

measures

Low

Clay

Inert material that has

––

retained plasticity once

in place

Hydrocarbon resistance

––

Labour intensive,

––

weather dependent

and time consuming

activity in spreading

and compacting the

clay requiring significant

vehicle movements

May not be safe to carry

––

out installation whilst

tanks are in service

due to machinery

requirements

High (non-

––

combustible

thick malleable

layer)

Normally

––

covered

with top soil

layer which

provides further

resistance

Medium

Sand bitumen

Remains flexible after

––

installation

Resistant to puncture

––

Cracks can be repaired

––

easily using hot bitumen

Hydrocarbon resistance

––

Specialist small plant

––

required to work on bund

wall slopes

Limitations on application

––

for steep slopes

May require renewal

––

before 25 years

Not suitable for floors

––

Performance

––

not proven.

Expected to be

––

‘Medium’ based

on bitumen

road surfacing

performance in

vehicle fires

Material is

––

combustible

Low

Shotcrete

(spray applied

concrete)

Ease and speed of

––

installation as concrete is

sprayed on

Plant can be operated

––

from outside the bund if

necessary

Proven durability

––

Able to cast around

––

penetrations

Hydrocarbon resistance

––

Specialist contractors

––

required

Requires joints for

––

construction and

movement

Requires regular

––

maintenance of joint and

penetration sealants and

cracks

Can buckle under heat

––

Very Good

––

Joints and

––

penetrations are

weakness

Low

Poly-

vinylchloride

(PVC)

Resistant to oils and

––

water

Not resistant to fuels

––

Requires protective layer

––

Potential hidden

––

problems around seals

and penetrations

Base ground to be

––

prepared well, ie remove

stones, requires a layer

of gravel and sand/

geotextile before the liner

Requires specialist

––

installer to weld joints

Very Low

––

Burns readily if

––

unprotected

Medium

Poly-urethane

(PU)

Water resistant

––

Not resistant to oils and

––

fuels

Requires protective layer

––

Very Low

––

Burns readily if

––

unprotected

Medium