Local Fuel plc - Shoreham Oil Terminal

Safety Instrument System Functional Safety Assessment Stage 5

P & I Design Ltd

DOCUMENT NO: LF364100_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: B DATE: 07.06.2016

Tel: + 44 (0)1642 617444

PAGE 21 OF 51

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

Final Element:

The PILZ safety relay provides normally open volt free contacts. A 24V dc supply originating

in the Rotork actuator is fed through these contacts and back to the hardwired ESD circuit

contained with the actuator. The actuator is capable of being operated remotely, however,

without the 24V dc input to the ESD circuit the actually will fail closed.

It is certified to BS EN 61508 by SIRA for use in a SIL 2 SIS with HFT = 0. As it has fairly

recently being certified it also has a Systematic Capability assessment with a resulting SC3.

REVISION B OF FSA ACTUAL DEVICE SI-2Q REVISED DATA.

REVISION A - The value used for the actuator in LF364006_RPT utilises the average value

from the certified data. This FSA checked what the overall pfd of the SIS would be if the

worst case value was used, this changed the PFD

SYS

form 3.57x10

-3

to 3.94x10

-3

which is still

within the required 5.00x10

-3

required from the LOPA.

REVISION B - The value used for the actuator in LF364006_RPT_Revision B utilises the

worst config value 1.17x10

-3

value from the certified data. Resulting in a PFD

SYS

form

3.93x10

-3

which is still within the required 5.00x10

-3

required from the LOPA.