Table of Contents Table of Contents
Previous Page  71 / 101 Next Page
Information
Show Menu
Previous Page 71 / 101 Next Page
Page Background

Local Fuel plc - Shoreham Oil Terminal

Safety Instrument System Functional Safety Assessment Stage 5

P & I Design Ltd

DOCUMENT NO: LF364100_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: B DATE: 07.06.2016

Tel: + 44 (0)1642 617444

PAGE 22 OF 51

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

The second part of the final element sub-system is a PEKOS ball valve. Exida have certified

this component as SIL 3 capable. In accordance with BS EN 61511 the device can be used in

a SIL 3 with HFT = 1 and SIL 2 with HFT = 0 with a PFD of 1.48x10

-3

.

Calculation Summary:

REVISION B- From the supplied components and BS EN 61508 certification it confirms that

the system does comply to the requirements of a PFD and HFT for a SIL 2 SIS, with a PFD

SYS

of 3.93x10

-3

.