Table of Contents Table of Contents
Previous Page  226 / 443 Next Page
Information
Show Menu
Previous Page 226 / 443 Next Page
Page Background

Instrument Specification

CLIENT:

REV DATE

BY

CHKD

APPD

CLIENT REF.

Local Fuel PLC

A 05.05.15 DSR DBF

DBF

LFS-SIS1

The Shoreham Oil Terminal

P & I REF.

LF364002_SPC

SHT

1

OF

3

ITEM:

Level Switch

(Mechanical)

GENERAL

Tag Number

See Sheet 2

Service

Fixed Roof Tank High Level Switch

Area Classification

Sensor - Zone 0, Head Zone1

DETECTOR

Type

RF Admittance

ELEMENT

Material:

Rod

Stainless Steel

Insulation

PEEK

Screening

PEEK

Earth Tube

n/a

Seals

PEEK

Connection:

Size

See Sheet 2

Type

See Sheet 2

Rating

See Sheet 2

Insulation Length

See Sheet 2.

Screening Length

Mfr. Std.

Screening Length

Mfr. Std.

HOUSING

Material

Powder Coated Aluminium

Enclosure Class

IP66

Electrical Classification

ATEX II 1GD EEx ia IIC T5

Electrical Connection

M20 x 1.5 Cenelec

TRANSMISSION

Type

2 wire

Supply

24V dc

Output

Current

Load

n/a

Action

Alarm - 8mA, Normal - 16mA, Fault - 22mA

Electrical Connection

Terminals

OPTIONS

PROCESS

Fluid

Distillate/Additive

DATA

Temperature Min./Max

Ambient

Temperature Normal

Ambient

Pressure Min./Max

0/56 mBar

Pressure Normal

Atmospheric

Specific Gravity

0.8 to 1.1

MANUFACTURERS

Supplier

Drexelbrook

DATA

Model Number

S2RLT20000(see Sheet 2)Z

DOCUMENTATION

See Attached Documentation Specification

LS#-CPA2.SPC