Local Fuel – The Shoreham Oil Terminal
Gasoline Import - Safety Instrument System
P & I Design Ltd
DOCUMENT NO: LF364006_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: C DATE: 13.05.16
Tel: + 44 (0)1642 617444
PAGE 3 OF 23
Fax: + 44 (0)1642 616447
www.pidesign.co.uk1
REVISION HISTORY
Rev Description
A
Original Issue
B
Sections 6.1.2, 6.4 and 6.5 modified for imperfect testing of Sensor
Sections 6.3.1, 6.4 and 6.5 Modified for SI2.1Q actuator
Section 6.3.1 Modified for Local Fuel LOC figures.
C
Valve closing speed reviewed following change of actuator and subsequent proof
testing. Changes made to section 6.3.1
D
2
SCOPE
This document has been prepared for the Safety Instrument System (SIS) associated with the
overfill protection of storage tanks It is intended to reflect the life cycle of the SIS in accordance
with IEC 61508 & IEC 61511 and to be a working document throughout the life cycle of the
Safety System.
The installation of the SIS will consist of the installation of RF type level switches in all storage
tanks. The installation will also include an actuated valve in the gasoline import line feeding
the gasoline tanks. There will be an SIS monitoring panel installed in the switchroom. Alarm
and Status data will be provided on the SIS monitoring panel and in the operations office.
The valve will be set to slow close at around 90 seconds to allow for surge pressure generation.