Local Fuel – The Shoreham Oil Terminal

Gasoline Import - Safety Instrument System

P & I Design Ltd

DOCUMENT NO: LF364006_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 13.05.16

Tel: + 44 (0)1642 617444

PAGE 9 OF 23

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

The proposed IEC61511 Edition 2 has a new requirement for hardware fault tolerance

Table 6 of the standard is reproduced below:

Minimum hardware fault tolerance

(unless clause 11.4.6 applies)

SIL

0

1

2

1

X

2 (low demand mode)

X

2 (high demand mode)

X

3

X

4

X

The Safety IntelliPoint RF

TM

Series Point Level Switch is classified as a Type B device

operating in low demand mode and clause 11.4.6 does not apply. Thus in this instance, a

hardware fault tolerance of 0 allows for this single sensor to be used as a 1oo1 sensor for a

SIL2 application.

6.1.4 Sensor Subsystem Summary

From the enclosed calculations and fault tolerance checks the sub-system meets the

requirements of > SIL 2 with a PFD 8.57 x 10

-4

Document LF364013_RPT details Testing Procedures.