Local Fuel – The Shoreham Oil Terminal

Gasoline Import - Safety Instrument System

P & I Design Ltd

DOCUMENT NO: LF364006_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 13.05.16

Tel: + 44 (0)1642 617444

PAGE 11 OF 23

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

6.2.3 Safety Relay

Tag Numbers R252, R292, R332, R372, R492, R523, R572, R612, R652, R692. Note: No

Safety Relays on Additive Tanks.

The chosen relay is PNOZ S2 which has the following safety requirements:

The circuit is redundant with built in self monitoring

The safety function remains effective in the case of component failure

The correct opening and closing of the safety function is tested automatically in each

on-off cycle

Electronic fuse

The relay has the following features:

3 positively guided normally open safety contacts

Status indicators

Feedback control loop for monitoring of external switches

Feedback control loop in series with reset circuit

The relay is also fail safe on power failure i.e. safety contacts normally open.

From the Pilz Safety Relay Type PNOZ S2 Internal safety Integrity Details, the PFD is taken

as 2.13 x 10

-5

.

6.2.4 Logic Solver Subsystem Summary

The combined PFD for the logic solver subsystem is 3.98 x 10

-4

+ 2.13 x 10

-5

= 4.20 x 10

-4

From the enclosed calculations the sub-system meets the requirements of >SIL 2 with a

PFD

G

of 4.207 x 10

-4