Local Fuel – The Shoreham Oil Terminal

Gasoline Import - Safety Instrument System

P & I Design Ltd

DOCUMENT NO: LF364006_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 13.05.16

Tel: + 44 (0)1642 617444

PAGE 22 OF 23

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

P & I Design Ltd

PFD - Logic Solver Subsystem Calculation Sheet 2

www.pidesign.co.uk

Sheet Title:-

Version 5.8

Project:

Originator:

DSR

Client:

Checked:

DBF

Client Ref:

Approved:

DSR

Document:

Issue:

B

SIS Number:

Date:

09.05.16

Key:

Data Input Cell

Calculation Cell

Results Cell

Element 1

Element 2

Data Type

Data Type

2

3

2

Failure Rate/hr (λ)

PFD Value Certified

Trip Amplifier

9.00E-09

PFD Value

3.50E-08

3.47E-07

SFF ( 0 to 1.0 )

0.90

8.90E-08

Diagnostic Coverage (%)

84.00

9.00E-08

2.50E-08

5.35E-07

1.30E-10

0.83

0.90

1.79E-07

5.79E-11

49.72

84.00

SUB-SYSTEM DATA

24

365

0.0

100

25.0

1.79E-07

8.90E-08

9.00E-08

0

2226.2

n/a

49.7

3.98E-04

3.94E-04

Valid

257

B

NO

Failures - Dangerous, Detected (λDD)

P&F - KFD2-CRG-Ex1.D

LF364

Local Fuel

Shoreham Terminal

LF364101_CAL

LFS-SIS1

System Architecture

Sub System Item

FAILURE DATA

Failures - Safe, Detected (λSD)

Failures - Safe, Undetected (λSU)

Proof Test Interval (days)

Failures - Dangerous, Undetected (λDU)

FAILURE CALCULATIONS

Total Failures (λ)

Safe Fail Fraction

Total Dangerous Failures (λ

D

)

Calculated Diagnostic Coverage (%)

Mean Time to Repair (hrs)

LOOP CRITERIA ACHIEVED

Percent of detected failures that have common cause (βD)

Proof Test Coverage (C

PT) -

%

Operational Lifetime of SIF (LT) - years

CALCULATED DATA

Total System Dangerous Failure (λ

D(group)

)

Total System Dangerous Detected Failure (λ

DD(group)

)

Total System Dangerous Undetected Failure (λ

DU(group)

)

Fraction of undetected failures that have a common cause (β)

Channel Downtime (t

CE

)

Voted Group Downtime (t

GE

)

Mean Diagnostic Coverage

Fault Tolerance Check (BS61508 - 2:2010) has been met?

PFD Total (Perfect Testing)

PFD Total (Imperfect Testing)

SIL achieved (Including Fault Tolerance)

Spurious Trip Rate (years)

FAULT TOLERANCE CHECK

Device Type

Note Hardware Fault Tolerance Check not made - Type B components with a SFF of 60 to

<90% must have a hardware fault tolerance of 1 according to table 3 for SIL2 subsystems.

Thus a single device is not normally appropriate against this criteria. However the

manufacture has provided prior and proven in use assessments performed by Exida, which

confirm the device complies with the requirements of BSEN 61511 and can be used as a

single device in a SIL 2 application.