Local Fuel – The Shoreham Oil Terminal

Gasoline Import - Safety Instrument System

P & I Design Ltd

DOCUMENT NO: LF364006_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 13.05.16

Tel: + 44 (0)1642 617444

PAGE 18 OF 23

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

The proposed IEC61511 Edition 2 has a new requirement for hardware fault tolerance

Table 6 of the standard is reproduced below:

Minimum hardware fault tolerance

(unless clause 11.4.6 applies)

SIL

0

1

2

1

X

2 (low demand mode)

X

2 (high demand mode)

X

3

X

4

X

The Valve and actuator are classified as Type A devices operating in low demand mode and

clause 11.4.6 is not applied as the minimum HFT does not require reduction. Thus in this

instance, a hardware fault tolerance of 0 allows for the single final element to be used as a

1oo1 element for a SIL2 application.

6.3.3 Final Element (ESD Valves) Subsystem Summary

The combined PFD for the final element subsystem is 1.17 x 10

-3

+ 1.48 x 10

-3

= 2.65 x 10

-3

From the enclosed calculations and fault tolerance checks the sub-system meets the

requirements of >SIL 2 with a PFD

G

of 2.65 x 10

-3

6.4

System PFD

System PFD = Sensor Sub-System PFD + Logic Solver PFD + Final Element Sub-System

PFD

System PFD = (8.57 x 10

-4

) + (4.20 x 10

-4

) + (2.65 x 10

-3

)

System PFD = 3.93 x 10

-3

From the enclosed calculations each sub-system individually satisfies the requirements of >

SIL 2 together with the combined PFD which meets the requirements of > SIL 2 with a

PFD

SYS

of 3.93 x 10

-3

and meets the Risk reduction factor of at least 200.

Spurious trip rate calculated as 1 in 16 years which meets the target of less than 1 in 10 years.