INSTRUMENT/ELECTRICAL CABLE SCHEDULE

CABLE

CONDUCTORS

CABLE ROUTE

APPROX.

REMARKS

REFERENCE TYPE AREA No.

FROM

GLAND

TO

GLAND LENGTH

mm

2

TYPE

TYPE

METRES

CP2/FJB27

F10I

1.5

10 pair CP2 Panel

EEx'e'

FJB27 I.S. Junction Box

EEx'e'

200

FJB27/FM3

F05I

1..5

5 pair FJB27 I.S. Junction Box

EEx'e'

FM3 Fluorobenzene Batcher

EEx'e'

20

FM3/FJB27

E01I

1..5

1 pair FM3 DP Cell

EEx'e'

FJB27 I.S. Junction Box

EEx'e'

20

IP1/FM3

E01I

1.5

1 pair I/P1 Convertor

EEx'e'

FM3 Fluorobenzene Batcher

EEx'e'

20

P107/FJB27

E01I

1.5

1 pair P107 Level Switch - Offloading Pump

EEx'e'

FJB27 I.S. Junction Box

EEx'e'

20

P108/FJB27

E01I

1.5

1 pair P108 Level Switch - Knock-Out Pot

EEx'e'

FJB27 I.S. Junction Box

EEx'e'

20

Air Supply/Panel

! bore 6mm O.D.

1 80 psi Air Supply

N/A

Pneumatic Panel

N/A

10

AS/1750

! bore 6mm O.D.

1 Pneumatic Panel

N/A

Control Valve 1750 Positioner Air Supply

N/A

10

Control/1750

1 bore 6mm O.D.

1 Pneumatic Panel

N/A

Control Valve 1750 Positioner Contol Signal

N/A

10

TOTAL

330

Note : Refer to P&I Design Cable Specifications for details on Cable Type.

REFERENCE DRAWINGS

REV DATE BY DRN

CHK'D

APP'D

DESCRIPTION

PLANT

Simon Storage - Tyne Terminal

A 07/10/97 AS AS DRR DRR DRR DRR ORIGINAL ISSUE

TITLE

Fluorobenzene Tank 24 - I.S. & Tubing

B 13/10/97 AS AH DRR

DRR

240V DB Revised

SHEET 3 OF 3

CLIENT DRG No

REF NO SI347100.SCH