www.pidesign.co.uk2.2.2 General
The Safety Instrument function will operate as a demand mode system with demands placed
on the SIS of no greater than one event in ten years. This demand rate has been
conservatively determined from the calculations in the LOPA and is backed up by site
experience in the operation of existing high high alarms, where existing records demonstrate
the frequency as conservative.
The Safety Instrument System will be a hardwired logic system utilising analogue and digital
switches and safety relays.
As the import process is performed on a batch basis, no specific requirements requiring 1oo2,
2oo2 systems or specific requirements regarding nuisance tripping are considered necessary.
Immingham Storage Co Ltd will confirm the acceptability of the calculated spurious trip rate
after the SIS PFD is calculated.
Common cause failure is not normally a consideration on non-redundant systems with the
valves operated periodically. However, failures that could conceivably lead to a dangerous
state would be the tank side import/export valves failing to close in the event of a independent
high high level switch activation. Each valve is a simple valve actuated with a pneumatic
spring return actuator. A common cause failure of electrical power or air supply would lead to
all valves closing. Further failures which could lead to the valve failing to danger is air which
is saturated with water with the possibility of freezing in the exhaust of the actuator vent
restrictor or dirt clogging up the solenoid vent.
In this design, there will be no conceivable individually safe process states which, when
occurring concurrently, create a separate hazard apart from damage to ship, pipelines, hoses
or jetty arms occurring on the fast closing of the valves. Valves will be fitted with restrictors
to ensure slow closing.
The functional test will be an end to end test with a simulated independent high high level
derived from the level switch. The switches cannot be fixed in the override position.
On activation of a independent high high switch, the operating procedures will ensure that the
transfer is terminated before carrying out a check on the system. An assessment of the human
response time, to check that on an SIS trip the correct action has occurred, is required to be
carried out during commissioning.
New procedures will be developed with auditable actions to ensure that on activation of the
SIS, the import from ship or pipeline is immediately stopped. It will also be necessary to
check that the correct valves have closed, and flow has ceased as required by the Safety
Instrument System
At present a mean time to repair of 72 hours will be assumed. If site conditions detect that this
is not feasible, the calculation of the SIS will be reviewed.